ERV wired remote controller and multiple ERVs
ERV Wired Remote Controller
F3, F4
1 . Remove the back cover of the ERV wired remote controller .
2 . Connect the COM a (F3), COM B (F4) of the ERV wired remote controller to the F3, F4 terminal of the ERV PCB .
3 . Reassemble the back cover and the ERV wired remote controller .
• Maximum 16 ERV units can be connected to 1 ERV wired remote controller at once .
CAUtIoN
Setting the onoff controller
OnOff Controller
ERV interface module (MIM-n10)
• Maximum 16 ERV units can be connected to 1 ERV interface module
• Maximum 128 units (ex . ERV, duct indoor unit etc . ) can be connected to 1 OnOff controller .
NotE
• MaIn address:
- Required address for communication between ventilation systems .
- If the MaIn address is not set, address will be set automatically and virtual address will be assigned .
• RMC address: address of OnOff controller
ERV
ERV
F1, F2
CN4
ENGLISH-19
ERV
ERV