Connection To The Chimney; Air Entrance Into The Installation Place During Combustion - LA NORDICA Termo Isotta DSA Instructions For Installation, Use And Maintenance Manual

Table of Contents

Advertisement

Available languages

Available languages

CHIMNEY CAPS - DISTANCES AND POSITIONING
Inclination of the
roof
α α α α
15°
30°
45°
60°
6.

CONNECTION TO THE CHIMNEY

The appliances with automatic door closure (type 1) must function, for safety reasons, with the fireplace door closed
(with exception of the fuel loading phase or removal of ash).
The appliances that do not have automatic door closure (type 2) must be connected to their own flue. Functioning with
the door open is only allowed under surveillance.
The thermoheating stove has an upper fumes pipe. The junction pipe for the connection to the chimney must be the
shortest possible and the junction points of the single pipes must be hermetic. The connection to the chimney must be
performed with stable and strong pipes (we recommend a thickness of 2 mm). The pipe for smokes exhaust must be
fixed hermetically to the chimney. The diameter inside the connection pipe must correspond to the external diameter
of the smokes exhaust small trunk of the stove. This is ensured by pipes according to DIN 1298.
ATTENTION : whenever the connection passes particular composites of inflammable materials, all inflammable
materials within a range of 20 cm around the pipe must be replaced by non-flammable and heat resistant
materials.
For a good operation of the equipment it is essential that in the installation place it is introduced sufficient air for
combustion. This means that, through suitable openings, air must recirculate for the combustion, even with doors and
windows closed (see chapter 7).
The depression on the chimney (CHIMNEY EFFECT) must be 17 – 20 Pa (=1.7 – 2 mm of water column). The
measurement must be done always with the equipment hot (rating calorific value). When the depression exceeds 20
PA (2 mm of water column) it is necessary to reduce the same with the installation of an additional flue adjuster
(butterfly valve) on the exhaust pipe or in the chimney.
7.

AIR ENTRANCE INTO THE INSTALLATION PLACE DURING COMBUSTION

As the stoves take their combustion air from the installation place, it is MANDATORY that a sufficient quantity of air is
introduced in the installation room itself.
In case of tight doors and windows (for example houses built according to the energy saving criteria) it is possible that
the air entrance is not guaranteed, compromising the draught, the welfare and the security of the people. It is
necessary to guarantee a further air entrance through an external air intake, to be positioned in the nearby of the
appliance or through air connection towards outside or a near ventilated room, with the exception of thermal units
place or garages (FORBIDDEN).
The connection pipe must be flat with a minimum diameter of 120 mm, a maximum length of 4 m and with no more
than 3 bends. If there is a direct connection with the outside it must be endowed with a special windbreak.
The air entrance for combustion into the installation place must not be closed during the operation of the stove. It is
absolutely necessary that in the environment in which the stoves operate with the natural flue of the chimney, it is
introduced as much air as necessary for the combustion, i.e. up to 25 m
26
Distance between the roof
ridge and the stack
A (m)
< 1.85 m
> 1.85 m
< 1.50 m
> 1.50 m
< 1.30 m
> 1.30 m
< 1.20 m
> 1.20 m
UNI 10683/98
Minimum height of the stack
(measured from the outlet)
H (m)
0.50 m above the roof ridge
1.00 m from the roof
0.50 m above the roof ridge
1.30 m from the roof
0.50 m above the roof ridge
2.00 m from the roof
0.50 m above the roof ridge
2.60 m from the roof
3
/ora.
Termo ISOTTA – DSA
7199701 Rev.05 – EN

Advertisement

Table of Contents
loading

Table of Contents