TrilliumSeries Condensers - General

ADIABATIC PRE-COOLER WATER FLOW
A minimum water flow must be distributed over the Adiabatic Pre-Cooler as per Minimum Water Flow Rates. (See
table "Minimum Recommended Adiabatic Pre-Cooler Water Flow Rates", section "About Water Care" on page 1)
The water flow will depend on the supply water pressure, and can be set by adjusting the adjustment screw on the
water flow valve on the flow meter (See Figure below). Read off the water flow at the underside of the float.
Water Flow Adjustment Screw
Model
DCV-S9122-*
DCV-S9123-*
DCV-S9124-*
DCV-S9125-*
DCV-S9126-*
For water quality guidelines and for calculation of Practical Scaling Index, refer to the Operating and Maintenance
Instructions, section Water Care.
TrilliumSeries Condensers with Factory installed
Control Panel with Variable Frequency Drive
ELECTRICAL PANEL
All units are equipped with an electrical panel with variable frequency drive and programmable relay outputs.
When operating with VFD drives above nominal frequency be aware of the potential risk for motor overload
or mechanical damages.
22
W W W . B A L T I M O R E A I R C O I L . E U
Number of Fans
4 fans
6 fans
8 fans
10 fans
12 fans
Minimum Recommended Adiabatic Pre-Cooler Water Flow Rates
Minimum pre-cooler water flow
per unit
14 l/min
22 l/min
28 l/min
36 l/min
44 l/min