Raypak 185A Replacement Instructions Manual page 12

Pc board, temperature control & sensor
Hide thumbs Also See for 185A:
Table of Contents

Advertisement

Program Button
1) To access the program screen, press the Mode button
until the display reads OFF. Remove the four screws
holding the control cover on. Swing control panel down
so the back side of the board is visible (see page 30).
Locate the Program Mode button as shown in the figure
on pg. 32. Press the program button (5-7 seconds) until
SETdef appears on the digital display. Release the pro-
gram button.
2) Press the Mode button sequentially until the desired pro-
gram event is reached. There are 5 different events that
can be programmed. They appear in the sequence listed
below:
Resets board to factory default settings.
Resets faults in the History File.
Change from Fahrenheit to Celsius.
SPA setpoint maximum adjustment.
POOL setpoint maximum adjustment.
SETdef – Default Settings
Refer to step one above to access the program screen.
SETdef should appear on the screen. If not, press the Mode
button until SETdef appears on the digital display. Press
and hold both "UP" and "DOWN" buttons for 5-7 seconds
until 3 dashes (---) appear. This operation resets the operat-
ing program to its factory default values. Both the POOL and
SPA setpoints will revert to 65°F (18.5°C) and both POOL
and SPA maximum temperature settings will be 104°F
(40.0°C). Once this is done, reassemble the control panel.
Page 12
RESfl – Reset Fault History
Refer to step one above to access the program screen.
Press the Mode button until RESfl appears on the digital dis-
play. Press and hold both "UP" and "DOWN" buttons for 5-7
seconds until 2 dashes (--) appear. This operation resets the
Fault History file to "0" and clears all the stored faults. Once
this is done, reassemble the control panel.
F/Cfff – Fahrenheit to Celsius
Refer to step one above to access the program screen.
Press the Mode button until F/Cfff appears on the digital dis-
play. The digital display is capable of displaying Celsius as
well as Fahrenheit temperatures. The "UP" or "DOWN" but-
tons will select "F" or "C" on the temperature display. Choose
the desired temperature scale. Once this is done, reassem-
ble the control panel.
SETspa 104 – SPA Set Point Maximum Adjustment
Refer to step one above to access the program screen.
Press the Mode button until SETspa 104 appears on the dig-
ital display. Using the "UP" and "DOWN" buttons will change
the Maximum Temperature Setting to your desired value.
The control can be set for a maximum of 107°F. Once this
is done, reassemble the control panel.
SETpool 104 – POOL Set Point Maximum Adjustment
Refer to step one above access into the program screen.
Press the Mode button until SETpool 104 appears on the
digital display. Using the "UP" and "DOWN" buttons will
change the Maximum Temperature Setting to your desired
value. The control can be set for a maximum of 107°F. Once
this is done, reassemble the control panel.
241169
P/N
Rev 4
Effective: 10-01-10
Replaces: 09-05-08