Specifications
The following specifications are typical for a range –40 to +70 °C,
unless otherwise noted.
Output
Number of channels.......................... 8
Output type ....................................... 24 VDC, sourcing
Supply voltage .................................. 5 VDC or 10 to 30 VDC,
Output current................................... 1 A, with built-in overcurrent
Output impedance............................. 0.3 Ω
Pulse-width accuracy ........................ –1, +3 µs, any period and
Physical
Indicators .......................................... Green POWER and
Weight............................................... 140 g (4.8 oz.)
Power Requirements
Power from network module ............ 300 mW
Environment
Operating temperature ...................... –40 to +70 °C
Storage temperature .......................... –55 to +85 °C
Relative humidity.............................. 5% to 90%, non-condensing
CE Mark Compliance
This product meets applicable EU directive(s), as follows:
Safety isolation ................................. EN 61010 (double insulation
FP-PWM-520
user-provided
protection circuitry,
8 A maximum for all
channels
duty cycle
READY indicators, 8 green
output state indicators
for 250 Vrms working
isolation, installation
category II)
8