Commissioning
4.5 Drive configuration for SIMODRIVE 611U
● This concludes the drive configuration. If there are no errors, the green 5 VDC LED and
The standard commissioning is now completed.
If you would like to use special functions of the SIMODRIVE 611U from the user program,
you should also read the Expert functions section.
See also
Important parameters on the SIMODRIVE 611U (Page 74)
72
Parameters to be entered directly:
P879 bit 13:
Enable the Equivalent zero mark function. This setting is necessary if you use the
Homing only homing cam" function. In addition, you must select the equivalent zero
mark function for input I0.x.
P880:
This specifies the scaling of the PROFIBUS speed value. For the maximum speed, a
setpoint NSET = 4000 0000 hex is transferred to the drive via the PROFIBUS. The
P880 parameter is used to inform the SIMODRIVE 611U which speed should be set
when NSET = 4000 0000 hex. This speed must agree with the "maximum motor
speed" value specified when the axis is created (Window axis configuration - Axis 1 -
Encoder number).
the yellow STOP LED are now illuminated on the technology CPU (the operating mode
switch is in the STOP position). The LED on the PROFIBUS module of the SIMODRIVE
611U is illuminated green.
Connecting the SIMODRIVE 611U to the Technology CPU
Product Information, 03/2008, A5E00272066-05