Viewing Events - Telect MIX 56 User Manual

Telect user manual ethernet connector
Table of Contents

Advertisement

4 Software Operation
MIX 56 by Telect

Viewing Events

4-44
Step
Action
1.
From the Directory screen, type 8 to select Alarm Thresholds and
press Enter.
The Alarm Thresholds screen appears.
Low Speed
---------
Alarm On
Alarm Off
--------
---------
AIS: 999
003
LOS: 002
003
Alarm On
--------
ES-15 min: 065
ES-24
hr: 648
SES-15 min: 010
SES-24
hr: 100
Redundancy Switch Status: Normal
2.
To set an alarm threshold, tab to the threshold field (ex. Low Speed
AIS Alarm On), type the number of seconds the condition must ex-
ist before triggering an alarm (Alarm On) or the number of seconds
the condition must be absent to turn off the alarm (Alarm Off), and
then press Enter.
3.
To enable redundancy switching, tab to the [Clear Lock] button and
press Enter. You can tab to this button only when redundancy
switching is locked.
The Redundancy Switch Status field displays "Normal" if not
locked, or displays "Locked Out" if locked. The [Clear Lock] but-
ton is only enabled if Status is "Locked Out".
Any occurrence in the MIX 56 system, whether initiated by a user or by the
system, is an event. You can view events in the Event Log, a screen that
displays the last 99 events.
MIX 56
Alarm Thresholds (in seconds)
----------------
High Speed
----------
Alarm On
--------
AIS: 002
RAI: 002
LOS: 002
OOF: 002
Alarm On
--------
ES-15 min: 025
ES-24
hr: 250
SES-15 min: 004
SES-24
hr: 040
[Clear Lock]
MIX 56 User Manual
Directory (Ctrl+D)
Help (?)
Alarm Off
---------
003
003
003
003
Telect, Inc. 122188-10 A0