LG Therma V Series Installation Manual page 90

Air-to-water heat pump
Hide thumbs Also See for Therma V Series:
Table of Contents

Advertisement

System Set-Up
• Function Code 28 and 29 : Setting control parameter for Sanitary water heating operation
Descriptions for each parameters are as following.
- Value #1 of Function Code 28 : temperature gap from Value #2 of Function Code 28.
- Value #2 of Function Code 28 : maximum temperature generated by AWHP compressor cycle.
- Example : If Value #1 is set as '5' and Value #2 is set as '48', then Session A (see the graph) will
be started when the water tank temperature is below 45°C. If temperature is above 48 °C, then
Session B will be started.
- Value #1 of Function Code 29 : temperature gap from target sanitary water temperature. This
value is required to frequent On and Off of water tank heater.
- Value #2 of Function Code 29 : Determining heating demand priority between sanitary water tank
heating and under floor heating.
- Example : If user's target temperature is set as '70' and Value #1 is set as '3', then the water tank
heater will be turned off when the water temperature is above 73 °C. The water tank heater will be
turned on when the water temperature is below 70 °C.
- Example : If Value #2 is set as '0', that means heating priority is on sanitary water heating, sani-
tary water is heated by AWHP compressor cycle and water heater. In this case the under floor can
not be heated while sanitary water heating. On the other hand, if the Value #2 is set as '1', that
means heating priority is on under floor heating, sanitary tank is ONLY heated by water heater. In
this case the under floor heating is not stopped while sanitary water is heated.
Water temperature
(Inside sanitary water tank)
Water heater off
temperature
Target sanitary water
temperature (set by user)
Value #2 of
Function Code 28
Starting temperature
of sanitary water heating
NOTICE
Sanitary water heating does not operate when it is disabled.
Enabling / Disabling of sanitary water heating is determined by pushing
When
icon is displayed on the control panel, sanitary water heating is enabled.
(by button input or scheduler programming)
90 Air-to-Water Heat Pump
Value #1 of
Function Code 28
Session A
Session B
Session A : Heating by AWHP compressor cycle and water heater
Session B : Heating by water heater
Session C : No heating (Water heater is Off)
Session D : Heating by water heater
Session C
Session D
Value #1 of
Function Code 29
Time
button.