Circuit Breaker Specification

• Select a power source that is capable of supplying the current required by the AWHP.
• Use a recognized circuit breaker between the power source and the unit.
A disconnection device to adequately disconnect all supply lines must be fitted.
• Capacity of circuit breaker recommended.
• Separate main power supply and heater supply.
Model
Power
Indoor
Outdoor
Supply
AHNW03604A2 AHUW036A2
AHUW056A2
AHNW09604A2
AHUW076A2
1~
AHUW096A2
220-240V
50Hz
AHUW126A2
AHNW16606A2
AHUW146A2
AHUW166A2
AHUW128A2
3N~
AHNW16809A2
AHUW148A2
380-415V
50Hz
AHUW168A2
Notes:
1. MCA / MOP
MCA = (1.25 x Load1) + Load2 + Load3
MOP = (2.25 x Load1) + Load2 + Load3
- Load1 : Rated running current of largest motor
(compressor or other motor)
- Load2 : sum of current for all other motors
- Load3 : any other load rated 1.0A or more
2. Select wire spec. based on the MCA
Core Component Electrical Spec.
Compressor
Electric Heater
Sanitary Tank Heater
RLA
FLA
Capacity
Power
RLA
Capacity
(A)
(A)
(kW)
Supply
(A)
(kW)
8
10
9.7
15
2+2
8.3
1Ø 230V
17
25
3+3
12.5
5.3
9.9
3+3+3 3Ø 400V 8.7
Piping and Wiring for Outdoor Unit
For
Heat Pump
Power
FLA
MCA
MOP
Circuit
Supply
(A)
(A)
(A)
Breaker (A)
9
16.6
20
13 23.9
20
3
1Ø 230V 12.5
22 40.3
40
6
11.1
10
3. Recommended circuit breaker is ELCB (Earth Leakage Circuit breaker)
4. RLA is measured during each individual compressor test condition.
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating Over current Protective device
RLA : Rated Load Amperes (A)
FLA : Full Load Amperes (A)
S/Heater: Sanitary Water Tan Heater
MCA, MOP & Circuit Breaker
For Electric Heater
For Electric Heater
(without S/Heater)
(with S/Heater)
MCA
MOP
Circuit
MCA
MOP
(A)
(A)
Breaker (A)
(A)
(A)
15
27
30
25
45
15
27
30
25
45
23
41
40
29
53
12
22
20
21
38
Installation Manual 45