Summary of Contents for Viessmann Vitotrol 200 RF

  • Page 1 VIESMANN Installation and service instructions for contractors Wireless base station For connecting a Vitotrol 200 RF and outside temperature sensor RF to a Vitotronic control unit For applicability, see the last page Wireless base station Please keep safe. 5692 915 GB...
  • Page 2 Safety instructions Safety instructions Please follow these safety instructions closely to prevent accidents and mate- rial losses. Safety instructions explained ■ all current safety regulations as defined by DIN, EN, DVGW, TRGI, Danger TRF, VDE and all locally applicable This symbol warns against the standards, risk of injury.
  • Page 3 ■ When using gas as fuel, also close the For replacements, use only orig- main gas shut-off valve and safeguard inal spare parts from Viessmann against unauthorised reopening. or those which are approved by ■ Isolate the system from the power sup- Viessmann.
  • Page 4: Table Of Contents

    Logging the wireless components on at the wireless base station...... Fitting the wireless repeater................. 10 Checking the transmission and reception quality of the Vitotrol 200 RF....10 Fitting the wall mounting base of the wireless base station......... 11 Inserting and removing the wireless base station..........11 Fitting the outside temperature sensor RF............
  • Page 5: Installation Sequence

    Installation sequence Installation location Connecting several remote control units Up to three Vitotrol RF and one outside temperature sensor RF can be connec- ted to a single wireless base station at any one time. Wireless connection Select the installation location of the wireless base station and the other wire- less components so that the radio sig- nals are beamed as vertically as possible...
  • Page 6: Connecting The Wireless Base Station To The Control Unit

    Installation sequence Installation location (cont.) Install the wireless base station as cen- Note trally as possible inside the building. Site Conducting metallic materials have a wireless components at least 0.5 m away strong negative effect on reception. from other transmitters (e.g. GSM, Prior to the final fitting at the chosen DECT, wireless LAN) and other HF sour- installation location, commission all wire-...
  • Page 7: Logging The Wireless Components On At The Wireless Base Station

    Installation sequence Connecting the wireless base station to the… (cont.) 7 6 5 4 3 2 1 3 2 1 A Wireless base station C Control unit with terminals X3 B Plug aVG to the control unit or to the D Control unit with plug-in connection KM BUS distributor Logging the wireless components on at the wireless base sta-...
  • Page 8 A on the wireless base station once for each compo- nent. 4. Initiate the logging on process at the relevant component. See the follow- ing chapter. Logging on the Vitotrol 200 RF Vitotrol 200 RF installation and service instructions...
  • Page 9 Installation sequence Logging the wireless components on at the… (cont.) Logging on the outside temperature sensor RF 1. Only if the outside temperature sen- sor is not logged on together with the other components: Initiate the logging on process at the wireless base station (see page 7).
  • Page 10: Fitting The Wireless Repeater

    Checking the transmission and reception quality of the Vitotrol 200 RF To determine the most favourable place See the diagnosis chapter or the Vitotrol to install a Vitotrol 200 RF, check the installation and service instructions. transmission and reception quality at the intended installation location.
  • Page 11: Fitting The Wall Mounting Base Of The Wireless Base Station

    Installation sequence Fitting the wall mounting base of the wireless base station Inserting and removing the wireless base station Insertion...
  • Page 12 Installation sequence Inserting and removing the wireless base station (cont.) Removal...
  • Page 13: Fitting The Outside Temperature Sensor Rf

    Installation sequence Fitting the outside temperature sensor RF Installation location: ■ North or north-western wall, 2 to 2.5 m above ground level; in multi storey buildings, in the upper half of the second floor ■ Not above windows, doors or ventila- tion outlets ■...
  • Page 14 Logging off components If a faulty component has been replaced ■ Logging off: or the wireless connection proved to be – Switch the control unit OFF and ON unstable, log all components off (includ- again. ing the wireless repeater, if installed) at –...
  • Page 15: Diagnosis

    Diagnosis Diagnosis on the Vitotrol 200 RF The Vitotrol 200 RF can display the 2. Call up a display of the transmission assigned heating circuits as well as the and reception quality with / : transmission and reception quality of the ■...
  • Page 16: Specification

    Specification Specification, wireless base station Power supply via KM BUS Rated voltage 27 V +/- 3 V Rated current 40 mA Power consumption Radio frequency 868.3 MHz Safety category IP rating IP 30 Permissible ambient temperature ■ During operation 0 to +40 °C −20 to +65 °C ■...
  • Page 17: Parts List

    Parts list Parts list When ordering spare parts Parts not shown Quote part no. 7455214 and the position 080 Installation and service instructions no. of the part (as per this parts list). 081 Operating instructions Obtain standard parts from your local 100 Plug supplier.
  • Page 20 Applicability Serial No.: 7455214 Viessmann Werke GmbH&Co KG Viessmann Limited D-35107 Allendorf Hortonwood 30, Telford Telephone: +49 6452 70-0 Shropshire, TF1 7YP, GB Fax: +49 6452 70-2780 Telephone: +44 1952 675000 www.viessmann.com Fax: +44 1952 675040 E-mail: info-uk@viessmann.com...