Enter programming mode by pressing [ENTER] during the initial power-up period after the chaser
sequence (while radio status LEDs are flashing consecutively or in unison).
The 7835C reads its EEROM to determine its preprogrammed parameters. A CRC of the EEROM
locations is also read. If the computed CRC does not match the one read from EEROM, or if the
programming parameters are invalid, the 7720P LCD displays "NO PROG" and the radio status LEDs flash
in unison (after the initial chaser sequence). Otherwise, the LEDs flash consecutively.
Password Protection
If you are NOT programming the radio through an ECP capable control panel (e.g., VISTA-128FB), the
programming menu can be password protected
Once a password is assigned, the following prompt appears upon entering programming mode:
See "Exiting Program Mode" paragraph later in this section for assigning and changing passwords.
Subscriber Information (Questions 1-7)
Question 1*.
Question 2.
Question 3.
Question 4.
Question 5.
Question 6.
ENTER PASSWORD:
Press "Y" to enable ECP communication for alarm input (check that
ECP Radio(Y/N)
* This question will NOT appear if you are programming via the control
If 7835C was previously registered and the alarm input mode has been changed (zone
trigger to ECP mode or vice versa) the 7835C must be re-registered.
ID #
City
CS ID
Supervision
(24Hr.)
Time Zone
(Eastern)
jumper P3 is to right). Press "N" to enable voltage triggers for alarm
input.
panel, since ECP mode is automatically required; Question 2 will be the
first programming option displayed on the keypad.
Enter the 4-digit customer account number, 0001-9999.
Enter the 2-digit primary city code, 01-99 (decimal).
Enter the primary central station's system ID number, 01-FE.
This selection sets the supervision timing for the 7835C for either 24
hour or weekly. The default supervision timing is 24 hours. The 7835C
sends a supervision message once during the supervision period.
AlarmNet transmits a communications failure alarm to the central station
if the supervision message is not heard within the period.
Use the Space key to select weekly or 24 hour supervision.
Must be set to 24 hr for UL installations.
Use the [SPACE] key to select the time zone in which the 7835C is being
installed: Eastern, Central, Mountain, Pacific, or Atlantic.
– 12 –