(see diagram). Several valves and diffusers can be connected to the same ventilation unit (one main module per ventilation unit). 12 VDC sensor (optional) VMX Contact IN module (optional) Motorised valves(s) VMX Main Module (compulsory) VMX Relay OUT module (optional) Optical sensor(s) (optional) VMX IN/OUT 0-10 V Module (optional) Diffuser(s) TF5814GB_E Aereco S.A.
VMX VFT Base for VFC series TROX valves Helical jet input or output airflow TROX XARTO diffuser. Airflow 324 to 990 m Diffuser XARTO Exists in different designs, with a round or square facing. On special request only. TF5814GB_E Aereco S.A.
0-10 V input To communicate the rate of ventilation To control a 0-10 V system in System with 0-10 V accordance with the rate of input, fan with ventilation 0-10 V input TF5814GB_E Aereco S.A.
- or IN/OUT 0-10 V if control is proportional Frequency (or voltage) regulator or power relay (if motor > 0.5 A at Diffuser maximum) Diffuser * in the case of a voltage regulator, replace the Relay OUT module with an IN/OUT 0-10 V module TF5814GB_E Aereco S.A.
V+ (use a specific colour for this wire). 0 V S 0 V E Section 1.5 or 2.5 mm². Motorised valve for the VMX system *supplementary power supply for the CO module only TF5814GB_E Aereco S.A.
0-10 V module connected to the frequency or module 2 voltage regulator of the fan. "Full or little" control requires a VMX Relay OUT module connected to the fan (via power relay if the fan is > 0.5A) module 1 TF5814GB_E Aereco S.A.
VMX S-PRE Optical sensor(s) VMX IN/OUT 0-10 V module C2 circuit breaker Note : Each module contains 2 black terminals and 2 orange terminals to make wiring simpler and minimize the use of connector boxes. module 1 module 2 TF5814GB_E Aereco S.A.
· 20 % ventilation = 2 minutes with ventilation + 8 minutes without ventilation · 30 % ventilation = 3 minutes with ventilation + 7 minutes without ventilation · etc. With 3 wires, the valves can open simultaneously. TF5814GB_E Aereco S.A.
The spurs should be nal flow of 210 m3/h on this valve, add the necessary spurs required to sunk right in, without spaces. block the shutter on position 6 as shown in the diagram below. TF5814GB_E Aereco S.A.
Open the shutter fully (shutter on the valve axle) Clip the drive onto the base as per the diagram, then block the drive The valve is assembled, ready to be installed and connected. by turning it clockwise. TF5814GB_E Aereco S.A.
> need memorization on the MAIN open closed closed module 6.7. MAINTENANCE The valves do not require any maintenance. Any failures which may occur are reported directly on the main module. TF5814GB_E Aereco S.A.
Change of the mode of the VMX Main module · Jumper not present: minimum ventilation reaches 0% ("full or none") N.B. the release jumper can be subsequently repositioned at any moment. A new memorisation of the main module will then be required. TF5814GB_E Aereco S.A.
The flashing light indicates the launching of the start-up cycle. The flashing light can perform from one to five cycles. Once the start-up cycle has been completed, you can proceed to configure the system at the main module level. TF5814GB_E Aereco S.A.
Return to factory configuration (only in the case of malfunction) · turn off the system (circuit breaker) · turn the system back on (circuit breaker) by pressing the memorisation button on the main module until the LEDs start flashing. TF5814GB_E Aereco S.A.
· designed to be mounted on the DIN rail in a power box (width corresponding to four electrical modules) This supply has been validated for EMC. The use of another power supply is under the responsibility of the installer or specifier. Aereco declines any responsibility in case of malfunctioning or damage. MODEL AVE1227 Input Voltage 110 –...
4,2 m maxi R = recommended overlap 0,4 m, mini 0 m, maxi 1m. r = recommended detection radius Respect the symmetry of the sensors in relation to the axis of the zone. 2 m, maxi 2,8 m TF5814GB_E Aereco S.A.
· modulation of airflow by a motorised valve (multizone) or by acting on the fan speed (unizone). The ventilation flow diminishes every 10 mins in steps of 10% as shown in the graph opposite, returning to 100% when a movement is detec- ted. TF5814GB_E Aereco S.A.
10 mins a maximum of 10% (in order to ventilate the premises sufficiently after all the occupants have left). But where necessary it can increase by n x 10% in the following cycle, according to requirements. 8.9. MAINTENANCE No specific maintenance is required. TF5814GB_E Aereco S.A.
· power supply and transfer of information via VMX specific bus · the sensor is connected to the system by just 3 wires with a section of 1.5 or 2.5mm² · Maximum number of CO sensors per main module: 1 TF5814GB_E Aereco S.A.
4. Install the sensor on the ceiling or on the wall, in a place where the level of CO can be detected in accordance with the instructions for installations detailed before (position). 5. Connect the wires according to the electrical diagram of the system provided in this document. TF5814GB_E Aereco S.A.
Just as for the "full or little" mode, the flow diminishes every 10 mins a maximum of 10% (in order to ventilate the premises sufficiently after all the occu- pants have left). But where necessary it can increase by n x 10% in the following cycle, according to requirements. TF5814GB_E Aereco S.A.
Taking into account the slow circulation speed at the level of sensitive elements, the measurement of CO is not affected by dust or water vapour. The sensor does not require recalibration during its life cycle. It has two infra-red sources with different operating cycles, which enables it to be recalibrated automatically. TF5814GB_E Aereco S.A.
Interpretation of sensor signals BEHAVIOUR OF THE LEDS Default (fast) (x4) Closed (flashes) Open (flashes) (flashes) INTERPRETATION configuration change without new open closed system not configured a module or a sensor is not working correctly memorisation of main module TF5814GB_E Aereco S.A.
· connected to the bus by two wires with section 1.5 or 2.5 mm² (flexible or rigid) · maximum number of Relay OUT modules per main module: 2 Relay Terminal: · external communication (lighting up a lamp, etc) TF5814GB_E Aereco S.A.
Contact 2 (flashes) Contact 1 (flashes) Contact 1 Contact 2 change of configuration without new a module or a sensor is not Contact 1 open Contact 2 open closed closed configured memorisation of the main module working correctly TF5814GB_E Aereco S.A.
· connected to the bus by two wires with section 1.5 or 2.5 mm² (flexible or rigid) · maximum number of Contact IN modules per main module: 2 CTS1, CTS2 Terminal: · receives external information to start up or shut down ventilation immediately. TF5814GB_E Aereco S.A.
V => 0 % motion, 10 V => 100 % motion) - Ventilation %: level of ventilation (0-100%) (level of ventilation calculated on the last 10 minutes, 0 V => 0 % ventilation, 10 V => 100 % ventilation TF5814GB_E Aereco S.A.
· connected to the bus by two wires with section 1.5 or 2.5 mm² (flexible or rigid) · maximum number of IN OUT 0-10 V modules per main module: 1 IN, OUT Terminal: · external communication (BMS for example) TF5814GB_E Aereco S.A.
Nevertheless, other types of diffusers may be used, providing the diameters are compatible with the network and the flows they offer are compatible with those of the VMX system valves. Where diffusers other than those offered by Aereco are chosen, special attention must be paid to the acoustic performance and air diffusion of the selected product.
33 / 34 14. FANS Aereco offers different models of fans compatible with the VMX system. Their pressure regulation system, low consumption and flows ranging from 500 to 6,000 m /h make the VCZ and VTZ models particularly suitable. The VCZ model is intended for an interior installation protected from the rain or indoor installation in its outdoor version. The VTZ model is intended for an external installation on the roof.
Page 34
Aereco S.A. 62 rue de Lamirault Collégien 77615 MARNE LA VALLEE CEDEX 3 FRANCE www.aereco.com...
Need help?
Do you have a question about the VMX Series and is the answer not in the manual?
Questions and answers