Using ʻSW101ʼ, Select the option of control function as described below.
- Operation Status output
Notes
Default status is all off.
• Operation status output : SW101 L4
Position
ON
ON : Activate Digital Output according to Indoor Unit status
OFF : Activate Digital Output according to Outside Unit status
L1 2 3 4
Depends on SW101 L4 position(ON/OFF), VWCK(Board) is operated as below
Dip Switch
SW101 L4 ON
SW101 L4 OFF
CAUTION
After change DIP SW setting, press reset switch to reflect the setting.
SW101
When even one of indoor unit (Remote controller) is turned on → Relay on
All Indoor are turned off → Relay off
When even one of compressor is turned on → Relay on
All compressor are turned off → Relay off
Function
VWCK(Board) operation
Setting and Using Method
Wiring
Operation
status
Installation manual 17