VP512A UNIT VENTILATOR VALVE
7/16
(11)
ADJUSTMENT
NUT
Fig. 3. Actuator removal (when necessary).
��������������������������������
���������
������������������������
������������������������
95-1785EF
J.H. 3-02
F
J
C
D
Fig. 2. Approximate dimensions in in. (mm)
1 PULL TAB OUT
TO RELEASE
STEM
2 DO NOT DISTURB
HEX HEAD
SETSCREW
3 LOOSEN
SETSCREWS (2)
4 LIFT ACTUATOR
FROM BONNET
M18804
�����������������������������������
����������������
��������������������
�������
NEAREST OBSTRUCTION
5-1/8
(130)
ALLOW 3-3/8 IN. 9 86 MM) APPROX
FOR REMOVAL OF ACTUATOR
FROM VALVE
3-5/8
STEM
(92)
BUTTON
3/8
(10)
A
E
B
SWING
RADIUS
CHECKOUT AND TESTING
With a 0 to 30 lb/in
line, vary branch line pressure. The difference between
the pressure at which the stem begins to move and the
pressure at full close off indicates the operating range.
The valve begins to close at 3 or 6 lb/in
and is fully closed at 8 or 11 lb/in
depending on the application.
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
H- SWING RADIUS
(TO TOP OF STEM
BUTTON WITH
ACTUATOR REMOVED
AND VALVE CLOSED)
G
M18805
2
(0 to 205 kPa) gage in the branch
2
(21 or 40 kPa)
2
(5 or 76 kPa),
customer.honeywell.com