Download Print this page

Carrier 120 Series Installation, Start-Up, And Operating Instructions Manual page 7

Multipoise oil furnace

Advertisement

24°V Wiring
Instructions
%r wiring
thermostat
(field
supplied)
are packed
in
thermostat
box
Make them_ostat
connections
as shown
in Fig. 3 or
4 at 24=v terminal
board on ihn timer board.
Accessories
When
installing
optional
accessories
to this
appliance,
follow
manufacturer's
Installation
Instructions
included
with
accessory.
Od-ler than wiring
fbr themaostat,
wire with a minimum
of type "T"
insulation
(63C>F rise)
nmst be used for accessories.
HORIZONTAL
OR DOVv_FLOW
INSTALLATION
For horizontal
installation,
determine
which "side" will become
the
"top", when
d_e unit is laid down.
Remove
the flue pipe clearance
knock=out
fi'om the top of that side panel. Install
the flue elbow so
that it exits the cabinet
of d_e ft/mace
through
that opening.
For counterflow
installation,
the flue pipe must
exit
the cabinet
through
1 of the side panel openings
(as above),
then extended
up
the side of the furnace.
Insure
that adequate
clearances
to con>
bustibles
are
observed.
Downflow
Conversion/Vent
Guard
Kit
MUST
be used.
Remove
burner
by loosening
mounting
nuts and mrn oil burner
slightly
counterclockwise
to unlock
the key hole burner
flange.
Prevent
putting
undue
strain
on burner
wiring.
(It may be neces=
sa V to disconnect
burner
wiring
in some cases.)
To reinstall
burner,
insert
on the four burner
studs
on key hole
burner
flange
and turn it clockwise
to lock it and dghten
nuts.
IMPORTANT:
Burner
retest always
be installed
in the upright
position
with
ignition
control
on top.
FILTERS
Never
operate
unit without
a fiher
or with filter
access
door
removed.
Failure
to adhere
to this warning
could
lead to a
hazardous
condition
which
could
lead to equipment
damage
and bodily
harm
An external
filter
rack
is provided
as standard
equipment
with
furnace
A sufficient
clearance
should
be provided
tbr air filter
access
See Table S i\_r filter rack flange
dimensions
for return air
duct
Tab{e 8--Filter
and Flange (In.)
UNIT
AIR NLTER
FLANGE OPENING
SIZE
SBZE
SRZE
10x24x1
105-12
or
15 X 23
16X25X1
t20-20
20 X 30 X 1
19 X 20
START-UP,
ADJUSTMENT,
AND
SAFETY
CHECKOUT
Step
l--Operational
Checkout
DO NOT
TAMPER
WITH
UNIT OR CONTROLS
(7ALL
YOUR
SERVICE
TECHNI(IAN.
Failure
to follow
this
warning
could
result
in personal
and/or
property
damage
Installation
of fmnace
is now complete
Run through
the ibltowing
checkout
and ensure
each item has been
peribm_e&
1. (orrect
nozzle
size has been
selected
for desired
input rate.
2. Blower
wheel support
is removed.
3. Electrical
wiring
is completed
according
to Fig. 3 or 4.
4. Blower
access
door is secured
in place
5. Valve on oil supply
line is open.
6
RESET
BUTTON
on primaD"
control
is pushed
down
7
Flame
observation
door and 2 cleanout
access doors located
at
fi'ont of unit are closed.
8. Thermostat
is set for
heating
mode
and
set above
room
temperature
If all of the above items have been perfbrmed,
set main electrical
switch
to ON position
and burner
should start. When burner
starts,
proceed
to Combustion
Check
section.
Step
2--Combustion
Check
In order
to obtain
optimum
per%rmance
from
oil burner,
the
following
setup procedures
must be followed:
1
A test kit to measure
smoke,
stack
draft,
over-fire
draft,
oil
pmnp pressure,
(02,
and stack temperatures
MUST be used in
order
to obtain
proper
air band
setting.
Although
all of the
above
measurements
are required
_br optimum
setup
and
efficiency
data, the most impmlant
readings
that must be taken
are
smoke
number,
over-fire
&aft,
stack
draft,
and
pmnp
pressure
2. The proper
smoke
nmnber
has been established
by engineer-
ing tests to be between
0 and 1. This degree of smoke
emission
is commonly
referred
to as a "trace"
of smoke.
It is recom-
mended
m use
a Bacharach
hue
spot
smoke
test
set or
equivalent.
3. In order to ensure
proper
draft through
fhrnace,
a barometric
draft regulator
(supplied
with furnace)
retest be installed.
In order fbr this device
to fhnction
properly,
barometric
damper
must be mounted
with hinge
pins horizontal
and face of damper
vertical.
(See instructions
included
with damper.)
The draft regu-
lator should be adjusted
after furnace
has been firing fbr at least 5
minutes,
and set between
-0.025
and -0.035
in. wc. (See Table 9.)
4. The over-fire
&aft,
which
is taken
through
observation
door
(located
in center
line above burner
in ii'ont panel
of furnace),
is a measurement
necessary
to detem_ine
if there is a blockage
between
oil burner
and flue outlet.
There should be a total pressure
drop of between
0.020 and 0.05 in.
wc through
furnace
as shown
in Table
9. The over-fire
draft must
be set within
the range
shown
in Table 9.
TaRe 9--Furnace
Draft Conditions
(In. WC)
FURNACE
FLUE
OVER-FIRE
TOTAL
RESTRICTION
iNPUT
DRAFT
DRAFT
THROUGH
{BTUH)
MINIMUt'V]
MAXIMUM
HEAT EXCHANGER
70,000
-0.025
0.010
0.020 to 0.035
91,000
-0.025
0.020
0.030 to 0.045
108,000
-0.025
0.025
0.035 to 0.050
110,000
-0.025
0.025
0.035 to 0.050
140,000
-0.025
0.025
0.035 to 0.050
154,000
-0.025
0.025
0.035 to 0.050
A reading
outside the range
shown in Table 9 (for example
+0.1 in.
wc) would
indicate
that f_lraace
is in an extremely
high-pressure
condition
in primary
section.
This condition
may be caused by any
of the following
problems:
a. Excessive
combustion
air due to air shutter being
too wide
open.
b
A lack
of flue
&aft
(chimney
effect)
or
some
other
blockage,
such
as soot,
in
secondary
section
of
heat
exchanger.

Advertisement

loading

This manual is also suitable for:

58cma