Download Print this page

Carrier 120 Series Installation, Start-Up, And Operating Instructions Manual page 4

Multipoise oil furnace

Advertisement

Donotblock combustion-air
openings
in thefurnace, Any
blockage
willresult inimproper combustion
which m ay r esult
inafirehazard an_or c ause bodily h arm
Step 2--General
This fhrnace should be installed in a location in which fi_cilities %r
ventilation permit satisfi_cto_- combustion of oil, proper venting,
and maintenance
of ambient temperature
at safe limits under
normal conditions of use. The location should not interfere with
proper circulation of air within the confined space. (See NFPA=3 !,
Section 1.5.)
In addition to air needed for combustion,
process air shall be
provided
as required
for: cooling
of equipment
or material,
controlling dew point, heating, @ing,
oxidation or dilution, safety
exhaust, and odor contml.
In addition to air needed for combustion, air shall be supplied for
ventilation,
including
all air required
for comfort
and proper
working conditions fbr personnel.
The barometric
draft regulator (included with Nrnace) shall be
installed in same room or enclosure as furnace in such a manner as
to prevent
any diffkrence
in pressure
between regulator
and
combustion=air supply.
Air requirements for operation of exhaust Rms, kitchen ventilation
systems, clothes dwers, and fireplaces
shall be considered
in
determining the adequacy of a space to provide combustion=air
requirements.
The tack of a proper amotmt of combustion air can lead to serious
Nrnace operational problems. Some of these problems are:
1. Excessive oil burner after-drip, and oil Nines.
2. Sooting.
3. Melted oil burner ignitor/relay control.
4. Air band or air mrbulator settings more open than nom_al
5. Lockouts on start=up
The requirements _br combustion and ventilation air depend upon
whether furnace is tocated in a (ONFINED
or [N(ONFINED
space.
Step a--Unconfined
Space
An unconfined space must have at 1east 50 cu k for each 1000
Bmh of total input [br all the appliances (such as furnaces, clothes
dwers, water heate*s, etc) in the space.
In unconfined spaces in buildings of conventional fi'ame, brick, or
stone construction, infiltration MAY be adequate to provide air for
combustion, ventilation, and dilution of flue gases This detem?i=
nation must be made on an individual installation basis and must
take into consideration the overall volume of'unconfined space, the
number of windows and ventilation openings, the number of doors
to the outside, internal doors which can close offunconfined
space,
and overall tighmess of building constluction
Conside*ation must
also be given to the amount of storage items (fi/rniture, boxes, etc.)
within the unconfined space which take away l"romthe air volume
(See Table 2.)
Many new buildings and homes (and older ones that have been
weatherized) MUST BE considered as being of tight construction,
therefore, infiltration will not be sufficient to supply necessary air
fbr combustion and ventilation.
Table 2--Mimmum
Floor Area
For Unconfined
Space
88CMA FURNACE
MINIMUM SQ FTWBTH
INPUT BTUH
7-tt2 FT CEILING
70,000
467
9%000
607
108,000
700
lt9,000
793
140,000
933
154,000
1026
A building
can be considered
as being
of tight constluction
when:
*
Walls
and
ceilings
exposed
to outside
atmosphere
have
a
continuous
water vapor retarder
with a rating of 1 perm or tess
with openings
gasketed
or sealed,
and/or
*
Weatherstripping
has been
added
on operable
windows
arid
doors
and/or
*
Caulking
or sealants
are applied
to areas such as joints
around
window
and
door
frames,
between
sole
plates
and floors,
between
wall-ceiling
joints,
between
wall panels,
at penetra=
tions
tbr plumbing,
electrical,
arid fhel
lines,
and
at other
openings
If combustion
and ventilation
air must be supplied
to an uncon=
fined
space from
outside,
an opening
with a FREE
AREA
of riot
tess than
1 sq in. per 1000 Bmh
of total input
of all appliances
within
unconfined
space
(but not tess
than
100 sq in.) must
be
provided.
This
opening
must
be located
such that it can not be
blocked
at any time.
Step
4--Confined
Space
A confined
space has a volmne
of less than 50 cu fl per 1000 Btuh
of the total input rating
for all appliances
installed
in that space
When
Nrnace
is installed
in a closet
or enclosure,
2 ventilation
openings,
with
OPEN
AREA
as dimensioned
in example
below
are required
for combustion
air. The openings
should
be located
about
6 in. from top and bottom
of enclosure
at ti'ont of fhrnace.
(See Table
3.)
TaRe a--Combustion
Air
From Confined
Space
58CMA FURNACE
LENGTH
INPUT NTUH
{BN.)
70,000-t 0S,000
16
t19,000
20
HEIGHT
(BN.)
g
q0
NOTE:
In calculating
free area,
consideration
shall be given
to
blocking
effect of louvers,
grilles,
or screens
protecting
openings.
Screens
used shall not be smaller
than
1/4-in.
mesh and shall be
readily
accessible
for cleaning.
If free area through
a louver
or
grille is known,
it shall be used in calculating
size and free area
specified.
If design and free area are not known,
it may be assumed
that wood louvers
have 20 percent
free area and metal
louvers
and
grilles
have 60 percent
free area. Louvers
shall be fixed
in open
position
or interlocked
with fi/mace
so they open automatically
at
furnace
start=up
and remain
open
during
It/mace
operation.
The size of the openings
depends
upon whether
the air comes from
outside
of the structure
or an unconfined
space inside the strt/cmre.
ALL
AIR FROM
INSIDE
THE STRUCTURE
For a confined
space, where
air is taken
from an interior
space,
2
pem_anent
openings
of equal area are required.
One opening
must
be within
12 in of ceiling arid the other within
12 in of floor. Each

Advertisement

loading

This manual is also suitable for:

58cma