Download Print this page

Carrier 120 Series Installation, Start-Up, And Operating Instructions Manual page 6

Multipoise oil furnace

Advertisement

TuNe 7--Electrical
Data
UNIT
SBZE
MAX WIRE
LENGTH
(FT)
VOLTS--
HERTZ--
PHASE--
115--60--1
115--60--1
OPERATING
VOLTAGE
RANGE
Max.*
Min.*
132
104
132
104
MAX
UNIT
AMPS
12.2
15.7
MIN
WIRE
GAGE
14
12
MAX FUSE OR
CKT BKR AMPS
t05-12
26
15
120-20
26
20
Permissible
limits of voEtage range at which unit will operate satisfactorily.
1 Length shown Js as measured
1 way alor_g wire path betweer_ u_it and service panel for maximum 2 percer_t vo{tage drop.
$ Time-delay
fuse is recommer_ded
2. Inspection
to ascertain
that vent
system
is clear
and fi'ee of
obstructions.
Any blockage
must be cleared
befbre
installing
fLli"nace,
3. Cleaning
chimney
or vent
if previously
used
fbr venting
a
solid fuel burning
appliance
or fireplace.
4. Confirming
that all unused
chimney
or vent connections
are
properly
sealed.
5. Verification
tiaat chimney
is properly
lined and sized per the
applicable
codes.
(Refer
to list of codes
in Safkty
Consider-
ations section.)
Mason_
Chimneys
This Nmace
can be vented
into an existing
masonry
chimney.
This
Nmace
must not be vented
into a chimney
servicing
a solid Net
burning
appliance.
Before
venting
Nmace
into
a chimney,
the
chimney
MUST
be
checked
fk)r deterioration
and
repaired
if
necessary.
The chimney
must be properly
lined and sized per local
or national
codes.
If Nrnace
is vented into a common
chinmey,
the chinmey
must be
of sufficient
area to accommodate
the total
flue products
of all
appliances
vented
into chimney.
The
fbllowing
requirements
are
provided
for
a safe
venting
system:
1. Be sure that chimney
flue is clear of any dirt or debris.
2. Be sure that chimney
is not servicing
an open fireplace.
3. Never
reduce
pipe size below
the outlet size of Nmace.
(See
Fig. 2.)
4. All pipe
should
be
supported
using
proper
clamps
and/or
stlaps.
These supports
should be at least every
4 ft.
5. Ail horizontal
runs of pipe should have at least 1/4-in. per ft of
upward
slope.
6. All runs
of pipe
should
be as short as possible
with
as f)w
rams
as possible.
7. Seams
should
be tightly
joined
and checked
for leaks.
8. The flue pipe must not extend into chimney
but be flush with
inside wall.
9. The chimney
n-rest extend
3 ft above highest
point
where
it
passes
through
the roof of a building
and at least 2 t't higher
than any portion
of a building
within
a horizontal
distance
of
10 ft. It shall
also be extended
at least
5 ft above
highest
connected
equipment
flue collar.
10. Check
local codes for any variance.
Factory=Built
Chimneys
Listed
_actory-built
chimneys
may
be used.
Refer
to chimney
manui_acmrer's
instructions
fbr proper
installation.
OIL BURNER
This fl/mace
is supplied
with
a high-pressure
atomizing
retention
head-type
burner
(fk_r use with grade
1 or 2 ft_el oil) The motmting
flange
is fixed to burner
air robe and no adjustment
is required
for
insertion
length.
OIL CONNECTIONS
Complete
instructions
for installing
fuel oil piping
can be _bund in
oil burner
Installation
Instrtlctions
included
with
furnace
Oil line
entry
holes
are provided
in side panels.
Two holes
are
provided
in each location
so that a 2-pipe
system
may be used if
desired.
An oil filter
should
be used
with
all oil burners
and should
be
installed
as close to burner
as possible.
BAROMETRIC
DRAFT
CONTROL
The barometric
draft control
shipped
with furnace
MUST
be used
with [_urnace to ensure proper
operation.
Instructions
fk}r installing
control
are packed
with control.
ELE( TRI( AL CONNECTIONS
N
The
unit cabinet
must
have
an uninterrupted
or unbroken
electrical
ground
to minimize
personal
injury if an electrical
fault
should
occur.
A green
ground
screw
is provided
in
contIol
box for this connection.
115-v Wiring
Befk_re proceeding
with
electrical
connections,
make
certain
that
voltage,
fiequency,
and phase
correspond
to that specified
on unit
rating plate. Also, check
to be sure that service provided
by utility
is sufficient
to handle
load imposed
by this equipment.
Refer
to
rating
plate or Table
7 fbr equipment
electrical
specifications
Make
all
electrical
connections
in
accordance
with
National
Electrical
Code (NEC) ANSI
NFPA
70-2001
and any local codes
or ordinances
that
might
apply
For Canadian
installations,
all
electrical
connections
must be made
in accordance
with Canadian
Electlical
Code CSA
C22.1
or subauthorities
having
jurisdiction.
Do not connect
ahmfumm
wire
between
disconnect
switch
and furnace
Use
only
copper
wire.
Failure
to fkfllow
this
caution
will lead to intermittent
electrical
operation
andor
fire hazard.
The contlol
system
depends
on correct
polarity
of power
supply.
Connect
HOT wire (H) and NEUTRAL
wire (N) as shown
in Fig.
3 or4.
A separate
line
voltage
supply
MUST
be used
with
a fused
disconnect
switch
or circuit
breaker
between
main
power
panel
and unit. (See Fig
3 or 4)
Metallic
conduit
(where
required/used)
may terminate
at side panel
of unit. It is not necessa_
to extend
conduit
inside unit f?om side
panel
to contlol
box.
When replacing
any original
furnace
wiring,
use only 105_>( No
14 AWG
copper
wire.

Advertisement

loading

This manual is also suitable for:

58cma