Download Print this page

Carrier 120 Series Installation, Start-Up, And Operating Instructions Manual page 10

Multipoise oil furnace

Advertisement

5_
6_
-->
?.
c. _se
of an oversized
nozzle
input
& Pump pressure
over values
listed iu Table
10.
The CO 2 and stack
temperature
instruments
enable
you
to
obtain
data required
to determine
thermal
efficiency
of _;ar=
*lace
An oil filter
should be installed
as close to burner
as possible
with
ALL
oil burners
and is essential
on lower
firing
rate
bumers_
We recommend
the use
of a tow pressure
drop oil
filter
such
as the
General
Filter,
Inc.
model
#lA-25A
or
equivalenL
The oil pressure
regulator
is factory
set to give oil pressure
of
130 psi J:br the model having
105,000 BTUH
input and 130 psi
fbr d'*e model
having
119,000
BTUH
input.
The firing
rate
noted
on nameplate
may be obtained
using
the nozzles
and
pump
pressures
indicated
in Tahle
10.
--> TaMe 10--Sumer
Input and Nozzle Size and Pump
Pressure
FURNACE
INPUT
REAL PUMP
INPUT
NOZZLE
USGPN
PRESSURE
(BTUH)
70,000
0.50
0.50-70VV
100
91,000
0.65
0.55-70B
140
105,000
0.75
0.65-70B
133
120,000
0.85
0.75-70B
128
140,000
1.00
0.85-70B
138
15&000
1.10
0.85-70B
167
SPECIFBCAT_ON
PUMP PRESSURE
100
140
130
130
140
170
8. On a new iustallation,
air entrapped
in oil lille leading
fiom
tank to nozzle
must
be thoroughly
purged
in order to prevent
excessive
after &ip.
The oil pump
is provided
with a special
fitting which
allows
purging
of ally air between
tank and oil
pump.
Tile proper
procedt/re
for performing
this operation
is
as £dlows:
a. Place
a piece of clear
plastic
1/4 in. diameter
robing
over
purge
fitdng
on oil pump.
b. Start oil burner,
then open purge fitting and allow burner
to
run until purge robe is completely
fi'ee of air bubbles.
c. Tighten
purge
fitting.
Allow
oil to run to nozzle
and fire
burner.
d. If purging
takes longer
than 15 sec and no flame has been
established,
burner
stops.
Push
reset
button
on fi'out
of
primary
control
to restart
burner
e. For detailed
information
on operation
of prima_
contloL
refer to instructions
included
with iq/rnace.
After
all the setup procedures
mentioned
above
have been
corn=
pleted,
the burner
should be allowed
to operate
and an inspection
rein'or
should be used to observe
the flame pattern
at tip of nozzle.
Any
irregularities
such as burning
to 1 side
or pulsating
flame
patterns
should
be connected
by changing
nozzle.
Step
3--Fan
Adjustment
Check
_his
f_lruace
is equipped
with
a 4=speed
direct-drive
motor
to
deliver
a temperature
rise within
range
specified
on rating
plate,
between
remm
and supply plenums,
at external
duct static pressure
noted
on rating
plate
When operating
furnace
in heating
mode,
static pressure
and
temperature
rise
(supply=air
temperatme
minus
return=air
temperature)
nlust be within
those
limits specified
on rating
label.
Failure
to follow
this warning
could
lead to severe
ftm]ace
damage.
Adjust
fan speed A(COPdDING
TO OIL INPUT
SELE(TED
so
that temperature
rise is within rise range
specified
on rating
plate.
(See
Table
110
Consult
wiring
diagram
for speed
changes
on
direct=&ive
motor
Tab{e 11--Speed
Selection
FURNACE
RECOMMENDED
UNiT
iNPUT
BLOWER
SIZE
(BTUH)
SPEED
70,000/119,000
Med-Low
105-t2/
120_20
91,000/140,000
Med-High
105,000/154,000
High
To adjust fire off time, set DIP switches
ou coutloi
board to obtaiu
desired
timing.
(See Fig. 5.)
60 Sec
90 Sec
120 Sec
150 Sec
DELAY
OFF DIP SWITCH
SETTINGS
A95115
Fig. 5--Fan
Off Time DIP Switch Settings
(Slack Box Represents
Switch
Posit{on)
Step
4--Limit
Controm
Check
After furnace
has beer* iu operation
_br at least 15 minutes,
restrict
return-air
supply
by blocking
filters
or closing
return registers
and
allow
furnace
to shut down
or* high limit. The burner
should
shut
off. and main blower
should
contkme
to rnn.
Remove
restriction,
and burner
should
come
back
on in a f_w
minutes.
Step
5--For
Year-Round
Air Conditioning
This
fitmace
is designed
£_r use
in cor_juncfion
with
cooling
equipment
to provide
year-round
air couditioniug_
The blower
has
been sized fbr both heating
and cooling,
however,
fan motor speed
may need to be changed
to obtain
necessary
cooling
airflow
Step
6--Heating
The blower
speed
is _i_ctory set to deliver
required
airflow
at
normal
duct static pressure.
Step
7--Cooling
The blower
speed may be field adjusted
to deliver
required
airflow
for cooliug
application.
(See Table
12)
10
Step
8--Constant
Blower
Switch
This _hruace is equipped
with a coustant
low=speed
blower
option.
Whenever
room
themlostat
is not calling
for heating
or cooling,
blower
runs
on tow
speed in order
to provide
air circulation_
If
constant
blower
option is not desired,
the rocker
switch
on top of
cabinet
may be used to mm off constant
speed.

Advertisement

loading

This manual is also suitable for:

58cma