Instruction Manual
Input range
Characteristic
Thermocouples
Sensor type
Measuring type
Standard
Averaging connection
Differentiating connection
SITRANS T3K PA
C79000-B7174-C55-04
9 resistance ranges selectable:
0 to 24 Ω
0 to 47 Ω
0 to 94 Ω
0 to 188 Ω
0 to 375 Ω
0 to 750 Ω
0 to 1500 Ω
0 to 3000 Ω
0 to 6000 Ω (not for averaging connection or
differentiating connection)
Resistance linear
Thermopairs
Type B: Pt30Rh-Pt6Rh
Type C: W5-Re
Type D: W3-Re
Type E: NiCr-CuNi
Type J: Fe-CuNi
Type K: NiCr-Ni
Type N: NiCrSi-NiSi
Type R: Pt13Rh-Pt
Type S: Pt10Rh-Pt
Type T: Cu-CuNi
Type T: Cu-CuNi
Type U: Cu-CuNi
Standard with 1 thermocouple with reference
point compensation or differentiating or
averaging connection value forming
1 thermocouple with or without reference
point compensation.
Averaging connection between the tem-
peratures of two thermocouples. The equiva-
lent value behavior is parameterizable (e.g.
the value of the other channel is output when
the channel is defective). The internal sensor
is used for reference point compensation.
Differentiating connection between the
temperatures of two thermocouples. The
difference is parameterizable (e.g. channel 2
– channel 1). The internal sensor is used for
reference point compensation.
7NG3213
DIN IEC 584
ASTM 988
ASTM 998
DIN IEC 584
DIN IEC 584
DIN IEC 584
DIN IEC 584
DIN IEC 584
DIN IEC 584
DIN 43710
DIN 43710
DIN 43710