Physical Specifications - Sun Microsystems StorEdge 3900 Series Site Preparation Manual

Hide thumbs Also See for StorEdge 3900 Series:
Table of Contents

Advertisement

TABLE 3
Specification
AC voltage rating
AC voltage range
Frequency range
Current at 240 VAC
Power consumption, maximum:
• Sun StorEdge 3910 system
• Sun StorEdge 3960 system
• Sun StorEdge 6910 system
• Sun StorEdge 6960 system
The following is recommended for all installations:
All AC mains and supply conductors to power distribution boxes for both the
cabinet system and the desktop system must be enclosed in metal conduit or
raceway, when specified by local, national, and/or other applicable government
codes and regulations. The supply conductors and power distribution boxes (or
equivalent metal enclosure) must be grounded at both ends.
The supplied storage systems require voltages within minimum fluctuation. The
facilities voltage supplied by the customer/end user must maintain a voltage of
not more than (+/-) 5%.
The customer facilities must provide suitable surge protection.

Physical Specifications

This section contains the physical requirements for the Sun StorEdge 3900 and 6900
series systems.
6
Sun StorEdge 3900 and 6900 Series 1.1 Site Preparation Guide • July 2002
Power Specifications for the System Cabinet
Rating
200 to 240 VAC
180 to 264 VAC
47 to 63 Hz
32A
4.2 kW
8.4 kW
4.2 kW
8.4 kW

Advertisement

Table of Contents
loading

Table of Contents