5.1.2
Fitting support bracket and mounting rail
▶ Secure the support bracket [4] to the wall, with appropriate fittings
[5] for appliance weight and wall type.
▶ Secure the wall mounting frame [6] to the wall, with appropriate
fittings [5] for appliance weight and wall type.
▶ Fit the pressure relief valve installer connector elbow [7] to the
pressure relief valve outlet.
– The connection elbow nut will be inside the casing when installed
allowing the pipe to drop below the bottom of the casing for
installation of discharge pipe-work.
5
6
Fig. 21 Support bracket and mounting rail
▶ Install and connect the pipe-work to the isolation valves on the
mounting frame and tighten the compression fittings, supplied in the
installation pack.
5.1.3
Example pipe-work installation.
The pipe-work to the appliance can be installed from below, above and a
mix of both.
A vertical pipe kit is available as an accessory, shown in figure 22.
Fig. 22 Pipe kit example
6 720 808 928 (2017/06)
4
5
7
5.1.4
Fitting the filling link assembly
Fit the Integral filling link, supplied with the appliance,
before hanging the appliance on the frame.
▶ The district water is treated and used to protect the
central heating system when this filling method is
used, section 6.9,Water quality for details on
typical additives used.
Refer to figure 23
▶ Ensure the isolation valves are closed on the district heating return
[1] and central heating flow connections [3].
NOTICE: There may be mains and system water
pressure behind the blanking plugs.
▶ Ensure all isolation valves are closed.
▶ Unscrew the blanking plugs [4] from the district heating return [1]
and central heating flow connections [3].
▶ Fit the filling link filter and "O" ring seals.
– Place the filter [7] inside the inlet of the filling link, ensuring that
the mesh is inside the filling link assembly [6].
– Fit the "O" ring seals [5] onto the inlet and the outlet of the filling
link assembly [6].
▶ Fit the filling link assembly onto the district heating return [1] and
central heating flow connections [3].
– Ensure that the filling link [6] is pushed in fully to the locating tabs
[8] on both sides of the assembly.
▶ Fit the securing screws and lock washers [2] in each of the isolation
valves.
1
7
5
6
4
8
Fig. 23 Filling link fitting
Installation
2
3
2
5
4
8
23