Key to Central heating performance chart, Figure 56:
[1]
Supply volumetric flow rate [l/s] and [l/h].
[2]
Supply flow temperature [ °C].
[3]
Supply differential pressure [kPa] (Standard unit).
[4]
Supply differential pressure [kPa] (Standard unit and heat
meter).
[5]
Supply differential pressure [kPa] (Standard unit and Differential
pressure control valve).
[6]
Supply differential pressure [kPa] (Standard unit, Differential
pressure control valve and heat meter).
Central heating example
The central heating performance chart, (figure 56, page 44) shows an
example for calculating the central heating performance.
• [a]
[ °C] Supply temperature = 65 °C
• [b]
50/30 °C (15.0 kW) Return temperature = 34.8 °C
• [c]
[l/s]/[l/h] Supply volumetric flow rate = 0.123l/s / 442.8l/
h
• [d]
[kPa] Supply differential pressure
– [Standard unit] = 6.8kPa
– [Standard unit with heat metre] = 10.9kPa
– [Standard unit with Differential pressure control valve] =
11.2kPa
– [Standard unit with Differential pressure control valve and heat
meter] = 15.5kPa
6 720 808 928 (2017/06)