D
• If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Wired remote controller
H0
H0 → Error code
Display messages do not apper even
when operation switch is turned ON
(operation lamp does not light up).
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• OPE lamp is blinking.
• The buzzer makes a short pipng sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)
LED2 (power for remote controller)
LED3 (communication between indoor and outdoor units)
• Wenn das Gerät nach dem obigen Probelauf nicht richtig betrieben werden kann, siehe folgende Tabelle zum Beheben der Ursache.
Schnurgebundene Fernbedienung
H0
H0 → Fehlercode
Auf dem Display erscheinen keine Mel-
dungen, auch wenn das Gerät einge-
schaltet ist (Betriebsanzeige leuchtet
nicht).
Bei der schnurlosen Fernbedienung im obigen Betriebszustand treten folgende Erscheinungen auf.
• Keine Signale von der Fernbedienung werden akzeptiert.
• OPE-Lämpchen blinkt.
• Der Signaltongeber gibt einen kurzer Piepton aus.
Hinweis:
Für etwa 30 Sekunden nach Beenden der Funktionswahl ist der Betrieb nicht möglich. (Korrekter Betrieb)
Eine Beschreibung jeder LED (LED 1,2,3), die mit der Steuerung der Innenanlage geliefert wurde, findet sich in der nachstehenden Tabelle.
LED 1 (Betriebsstrom für Mikrocomputer)
LED 2 (Betriebsstrom für Fernbedienung)
LED 3 (Kommunikation zwischen Innenaggregat und Außen-
aggregat)
Symptom
LED 1, 2 (PCB in outdoor unit)
For about 2
After LED 1, 2 are lighted, LED 2 is turned off,
minutes following
then only LED 1 is lighted. (Correct operation)
power-on
Only LED 1 is lighted. → LED 1, 2 blink.
After about 2
minutes has
expired following
power-on
Only LED 1 is lighted. → LED 1 blinks twice,
LED 2 blinks once.
Indicates whether control power is supplied. Make sure that this LED is always lit.
Indicates whether power is supplied to the remote controller. This LED lights only in the case of the
indoor unit which is connected to the outdoor unit refrigerant address "0".
Indicates state of communication between the indoor and outdoor units. Make sure that this LED is
always blinking.
Symptom
LED 1, 2 (Leiterplatte in Außenaggregat)
Für etwa 2 Minuten
LED 1 und 2 leuchten auf, dann LED 2 wird
nach dem
ausgeschaltet, nur LED 1 leuchtet. (Korrekter
Einschalten.
Betrieb)
Nur LED 1 leuchtet. → LED 1 und 2 blinken.
Wenn etwa 2
Minuten nach dem
Einschalten
Nur LED 1 leuchtet. → LED 1 blinkt zweimal,
vergangen sind.
LED 2 blinkt einmal.
Zeigt an, ob Steuerstrom anliegt. Sicherstellen, daß die LED immer leuchtet.
Zeigt an, ob Strom an der Fernbedienung anliegt. Diese LED leuchtet nur bei einem Innenaggregat,
daß an das Außenaggregat mit der Kältemitteladresse "0" angeschlossen ist.
Zeigt den Zustand der Kommunikation zwischen Innenaggregaten und Außenaggregaten an.
Sicherstellen, daß diese LED immer blinkt.
Cause
• For about 2 minutes following power-on, operation of the
remote controller is not possible due to system start-up. (Cor-
rect operation)
• Connector for the outdoor unit's protection device is not con-
nected.
• Reverse or open phase wiring for the outdoor unit's power
terminal block (L1, L2, L3)
• Incorrect wiring between indoor and outdoor units (incorrect
polarity of S1, S2, S3)
• Remote controller wire short
Ursache
• Für etwa 2 Minuten nach dem Einschalten ist der Betrieb
der Fernbedienung aufgrund des Anlagenstarts nicht mög-
lich. (Korrekter Betrieb)
• Der Steckverbinder für das Schutzgerät des Außenaggregats
ist nicht angeschlossen.
• Phasenverkehrt oder offene Phasenverdrahtung für Betriebs-
strom-Klemmenblock (L1, L2, L3)
• Falsche Verdrahtung zwischen Innen- und Außenaggregat
(falsche Polung von S1, S2, S3)
• Kurzschluß des Fernbedienungskabels
8
89