Fit The Flue Gas Pipe Sealing Collar (Optional Accessory); Fit The Flue Gas Temperature Sensor (Option) - Buderus Logano GE315 Installation And Maintenance Instructions Manual

Cast iron sectional boiler for oil or gas pressure jet burners
Table of Contents

Advertisement

2
Burner installation
2.6.6
Fit the flue gas pipe sealing collar
(optional accessory)
NOTE!
We recommend you use a flue gas pipe
sealing collar (Fig. 29, Item 1).
Insert the flue gas pipe until it contacts the flue gas
collector coupling.
Place the flue gas pipe sealing collar on the top so
that it overlaps the flue gas pipe and the coupling.
Place the jubilee clips (Fig. 29, Item 4) over the flue
gas pipe sealing collar. One of the jubilee clips must
clamp on the coupling of the flue gas collector and the
other onto the flue gas pipe.
Tighten the jubilee clips.
After the jubilee clips have been tightened the flue gas
pipe sealing collar must fit evenly and closely.
NOTE!
Re-tighten the jubilee clips a short time
after commissioning.
2.6.7

Fit the flue gas temperature sensor (Option)

Weld the coupling (Fig. 29, Item 3) at a distance of
2 x flue gas pipe diameter (A) – min. 720 mm – from
the flue gas collector into the flue gas pipe.
Install the flue gas temperature sensor (Fig. 29,
Item 2) in accordance with separate installation
instructions.
24
Fig. 29
Item 1: Flue pipe sealing collar
Item 2: Flue gas temperature sensor
Item 3: Coupling
Item 4: Jubilee clip
Item 5: Flue gas collector
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Logano GE315 • Issue 02/2006
2
1
3
5
4
min. 720 mm
Flue gas pipe installation