4 Programming
007
LCP copy
Value:
No copying (NO COPY)
Upload all parameters (UPL. ALL PAR.)
Download all parameters (DWNL. ALL PAR.)
Download size-independent parameters
(DWNL.OUTPIND.PAR.)
Function:
Parameter 007
LCP copy
panel's integral copy function. The function is used if you want to copy
4
all parameter setups from one adjustable frequency drive to another by
moving the LCP 2 control panel.
Description of choice:
Select
Upload all parameters
transferred to the control panel. Select
parameter values transferred are to be copied to the adjustable frequency
drive to which the control panel is attached. Select
pendent par.
[3] if you only want to downloade the size-independent
parameters. This is used when downloading to a adjustable frequency
drive with a different rated power size than that from which the param-
eter setup originates.
NB!
Upload/download can only be performed in stop mode.
Download can only be performed to a adjustable fre-
quency drive with the same software version number,
see parameter 626
008
Display scaling of output frequency
Value:
0.01 - 100.00
Function:
In this parameter, the factor is selected by which the output frequency is
to be multiplied. The value is shown in the display, provided parameters
Display readout
009-012
have been set to
Description of choice:
Set the required scaling factor.
009
Large display readout
Value:
No readout (none)
Resulting reference [%]
(reference [%])
Resulting reference [unit]
(reference [unit])
Feedback [unit] (feedback [unit])
Frequency [Hz] (Frequency [Hz])
Output frequency x scaling
(frequency x scale)
Motor current [A] (Motor current [A])
Torque [%] (Torque [%])
Power [kW] (Power [kW])
Power [HP] (Power [HP][US])
Motor voltage [V]
(Motor voltage [V])
68
is used if you want to use the LCP 2 control
[1] if you want all parameter values to be
Download all parameters
Download size-inde-
Database identification no.
Output frequency x scaling
MG.90.S1.02 - VLT
DC link voltage [V]
(DC link voltage [V])
[0]
Thermal load motor [%]
(Motor thermal [%])
[1]
Thermal load [%]
[2]
(FC. thermal[%])
Running hours [Hours]
[3]
(RUNNING HOURS])
Digital input [Bin]
(Digital input[bin])
Analog input 53 [V]
(analog input 53 [V])
Analog input 60 [mA]
(analog input 60 [mA])
[2] if all
Pulse reference [Hz]
(Pulse INPUT 33. [Hz])
External reference [%]
(external ref. [%])
Status word [Hex] (Status word [hex])
Heatsink temperature [°C]
(Heatsink temp [°C])
Alarm word [Hex] (Alarm word [hex])
Control word [Hex] (Control word [Hex])
Warning word [Hex]
(warning word [Hex])
Extended status word [Hex]
(Ext. status [hex])
Communication option card warning
1.00
(COMM OPT WARN [HEX])
Pulse count
(PULSE COUNTER)
Pulse input 29
[5].
(PULSE INPUT 29)
Function:
In this parameter you can select the data value that you wish to display
in the LCP control unit display line 2 when the frequency converter is
switched on. The display will also be included in the scrollbar in display
mode. In parameters 010-012
[0]
three data values, which are displayed in display line 1.
Description of choice:
[1]
No readout
can only be selected in parameters 010-012
readout
.
[2]
Resulting reference [%]
[3]
in the range from Minimum reference, Ref
Ref
.
[4]
MAX
Reference [unit]
gives the resulting reference with unit Hz in
In
Closed loop
the reference unit is selected in parameter 416
[5]
units
.
[6]
Feedback [unit]
gives the resulting signal value using the unit/scaling
[7]
selected in parameter 414
[8]
feedback, FB
and 416
HIGH
[9]
Frequency [Hz]
gives the output frequency of the frequency converter.
[11]
®
is a registered Danfoss trademark
®
VLT
Decentral FCD 300 Design Guide
Display readout
you can select a further
Small display
gives, as a percentage, the resulting reference
to Maximum reference,
MIN
Open loop
Minimum feedback, FB
, 415
LOW
Process units
.
[12]
[13]
[14]
[15]
[16]
[17]
[19]
[20]
[21]
[22]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
.
Process
Maximum