1-13-2. Setting of TRAP IP
1. Display the CONFIGURATION menu screen. (Refer to Section 1-12-1.)
2. Display the "SNMP TRAP" using [UP] or [DOWN] key.
SNMP TRAP
000.000.000.000
3. Press [ENTER] key to enter a new TRAP IP.
4. Repeat the following steps (1) and (2) to enter a desired TRAP IP address.
(1) Set a desired number using [UP] or [DOWN] key.
(2) Press [RIGHT] or [LEFT] key to move the cursor position.
5. Press [ENTER] key when the input is completed.
6. The check screen is displayed.
CHANGE
OK
NG
Set the cursor to OK using [RIGHT] or [LEFT] key and press [ENTER] key.
1-14. Setting of FAN MODE
A operation mode of fan installed in FAN UNIT is changed.
OFF: Normal mode (factory setting)
ON: Silent mode
1. Display the CONFIGURATION menu screen. (Refer to Section 1-12-1.)
2. Display the "FAN SILENT" using [UP] or [DOWN] key.
FAN SILENT
OFF
3. Press [ENTER] key. When the cursor appeared, change to ON from OFF using [UP] or [DOWN]
key and press [ENTER] key.
FAN SILENT
ON
4. The check screen is displayed.
CHANGE
OK
NG
Set the cursor to OK using [RIGHT] or [LEFT] key and press [ENTER] key.
1-18 (E)
NSS-S2