Table 65 - Warning Description Table - Johnson Controls 100 Series Installation Operation & Maintenance

Packaged rooftop units, single packaged units, ypal design level g
Hide thumbs Also See for 100 Series:
Table of Contents

Advertisement

FORM 100.50-NOM12
ISSUE DATE: 04/02/2019

TABLE 65 - WARNING DESCRIPTION TABLE

HISTORY
SCREEN
WORDING
Building static pres> 0.45" W.C. or <
WRN-BUILDING
-0.45" W.C. for 10 seconds. Power
PRS
exhaust reverts to none or on/off
WRN-CO2
Outside CO
SENSOR 1
15 minutes
OUTSIDE
WRN-CO2
Outside CO
SENSOR 2
15 minutes
INSIDE
WRN-COMPR
SYSTEM *
See description at the end of this table
INHIBIT
WRN-DIRTY
The filter status input is closed for >= 1
FILTER 1
minute
WRN-
The discharge pressure for that system
DISCHARGE PRS
is out of range for >= 10 seconds
SENSOR *
Supply fan output on, supply fan status
WRN-DUCT PRS
must be running for 5 minutes, static
XDCR
press current <=(0.333 X duct static
press active sp) for 30 seconds
The exhaust fan output is on for 45
WRN-EXHAUST
seconds and the run verification input is
FAN
low (open) for 10 seconds
WRN-
The hw/steam freezstat circuit goes
FREEZESTAT
high (closed) but goes low (open) within
TRIP
5 minutes
On modulating gas the heat binary
WRN-FURNACE
outputs do not match the gas furnace
MULTIPLEXER
status input. See Table 63 on page
FAULT
169 for furnace status input on staged
heat
The heat binary outputs do not match
WRN-GAS
the gas furnace status input. See Table
FURNACE
63 on page 169
WRN-HET
The heat entering sensor is out of range
SENSOR
for >= 10 seconds
Both compressor are on for the system
WRN-HIGH DP
and the discharge press is >= to the
UNLOAD *#
system unloading pressure for 10
seconds
WRN-LOW
The outdoor temp is <= to the mech
AMBIENT TEMP *
cool lockout temp
WRN-LOW
The suction temp is less than the
SUCTION TEMP
suction temp low limit for 10 continuous
*#
seconds
JOHNSON CONTROLS
DESCRIPTION
sensor out of range for >=
2
sensor out of range for >=
2
SHOW WHEN
RESET
UNIT TYPE IS
Power Exhaust
Auto
Other Than
Reset
None Or On - Off
Damper
Auto
Ventilation Control
Reset
Equals Demand
Auto
Ventilation Control
Reset
Equals Demand
Auto
Reset
Auto
Dirty Filter Switch
Reset
Is Installed
Press Trans Pkg
Auto
Is On For The
Reset
System
Auto
Unit Type Is VAV
Reset
Or FlexSys
Auto
Power Exhaust
Reset
Other Than None
Heating System
Auto
Type Equals Hot
Reset
Water Steam
Heating System
Auto
Type Equals
Reset
Modulating Gas Or
Staged Gas
Heating System
Auto
Type Equals
Reset
Staged Gas
Heating System
Auto
Type Is Staged
Reset
Gas Or Electric
Press Trans Pkg
Auto
Is On For The
Reset
System
Low Ambient Pkg
Auto
Is Not Installed For
Reset
The System
Auto
Reset
SECTION 8 – SERVICE
STATUS
FAULT
SCREEN
OUTPUT
WORDING
TYPE
Exhaust
Sensor/
Sys Status
Misc
Warning
Fault
Ventilation
Sensor/
Sys Status
Misc
Warning
Fault
Ventilation
Sensor/
Sys Status
Misc
Warning
Fault
Cooling
Heating
Fault
Sensor/
Filter Status
Misc
Change
Fault
Sensor/
Sensor/
Misc Status
Misc
Warning
Fault
Supply
Sys Status
Fan Fault
Warning
Exhaust
Sensor/
System Status
Misc
Warning
Fault
Sensor/
Cooling
Misc Status
Heating
Warning
Fault
Sensor/
Cooling
Misc Status
Heating
Warning
Fault
Cooling
Heating
Fault
Sensor/
Sensor/
Misc Status
Misc
Warning
Fault
Sensor/
Sensor/
Misc Status
Misc
Warning
Fault
Comp Sys *
Sensor/
Status Low
Misc
Amb Inhibit
Fault
Comp Sys *
Sensor/
Status Suction
Misc
Temp Unl # On
Fault
175
8

Advertisement

Table of Contents
loading
Need help?

Need help?