Troubleshooting Guide - Emerson NELSON HEAT TRACE SMMC-3 Manual

Table of Contents

Advertisement

TROUBLESHOOTING GUIDE

SYMPT OMS
System is not operating and system
light is not lit.
Display is not lit and power switch
is on.
System is not operating,
Temperature Standby on display.
Error!
SMTS-1 on display and
system not operating.
Error!
SMTS-1 on display after
corrections made.
Error!
SMPS-1 on display and
system not operating.
The aerial or gutter sensors are wet
(covered in snow), the LED above
the corresponding terminal block is
lit and the system is not heating.
The in-ground sensor is wet
(covered in snow), the sensor
surface is warm and system is not
heating.
n
TULSA, OK 74101 n
PO. Box 726
GA-2318, R1
Sheet 12 of 15
May 2008
PROBABLE CAUSE
No Power to SMMC-3
Supply not energized or power
input fuse burned out.
The SMMC-3 is in a standby mode,
the ambient temperature outside is
above the programmed
temperature required to melt snow.
There is a communication problem
with the temperature sensor
Need to clear SMTS-1 error from
SMMC-3 program.
There is a communication problem
with the in-ground sensor.
Possible communication problem
with the aerial or gutter sensor. No
error message will show on the
display when this occurs.
The surface of the in-ground sensor
may be dirty, possibly covered with
sealant.
TEL 918-627-5530 n
FAX 918-641-7336
CORRECTION
Turn on power using switch on front
panel.
Check power supply. If LED above
power input terminal connection is
not lit, replace fuse (4A spare fuse )
supplied with SMMC-3.
NORMAL OPERATION
Make sure the temperature sensor
lead wires are connected to the
terminal properly. If the sensor wire
has been extended, use 3
Conductor Instrumentation Cable,
#18AW G, unshielded, common
conductors such as twisted pair
communications wire, telephone
wire, electrical building wire and
doorbell wire is not acceptable.
Manufacturer: Belden #5301UE or
equal.
Turn off system using the front
panel switch, wait 10 seconds and
turn on again. The SMMC-3 should
now recognize the sensor.
Make sure the in-ground sensor
lead wires are connected to the
terminal properly. If the sensor wire
has been extended, use 4
Conductor Instrumentation Cable,
#18AW G, shielded, common
conductors such as twisted pair
communications wire, telephone
wire, electrical building wire and
doorbell wire is not acceptable.
Manufacturer: Belden #9418 or
equal.
Make sure the in-ground sensor
lead wires are connected to the
terminal properly. If the sensor wire
has been extended, use 3
Conductor Instrumentation Cable,
#18-20AWG, shielded or
unshielded, common conductors
such as twisted pair
communications wire, telephone
wire, electrical building wire and
doorbell wire is not acceptable.
Manufacturer: Belden #8770 or
equal.
Clean the sensor surface to get rid
of any contaminant, use mild
detergent and carefully scrub with
steel wool.