SPECIFICATIONS

Electrical
Power Requirements
120 VAC, 50/60 hz, 480VA
Control Relays
Outputs
120 VAC, Pilot Duty, 120VA
Power Supply
Sensors
24 VAC, Class 3, 12VA
Temperature Sensor Supply
5 VDC, Class 2, 0.5VA

SENSOR EXTENSION WIRE SPECIFICATIONS

Aerial Sensor SMAS-1
3 Conductor Instrumentation Cable, #18-20AWG, shielded or unshielded,
common conductors such as twisted pair communications wire, telephone wire,
electrical building wire and doorbell wire is not acceptable.
Manufacturer: Belden #8770 or equal
Gutter Sensor SMGS-1
3 Conductor Instrumentation Cable, #18-20AWG, shielded or unshielded,
common conductors such as twisted pair communications wire, telephone wire,
electrical building wire and doorbell wire is not acceptable.
Manufacturer: Belden #8770 or equal
Temperature Sensor SMTS-1
3 Conductor Instrumentation Cable, #18AW G, unshielded, common conductors
such as twisted pair communications wire, telephone wire, electrical building
wire and doorbell wire is not acceptable.
Manufacturer: Belden #5301UE or equal
Pavement Sensor SMPS-1
4 Conductor Instrumentation Cable, #18AW G, shielded, common conductors
such as twisted pair communications wire, telephone wire, electrical building
wire and doorbell wire is not acceptable.
Manufacturer: Belden #9418 or equal
n
TULSA, OK 74101 n
PO. Box 726
GA-2318, R1
Sheet 14 of 15
May 2008
Mechanical
NEMA 12 non-metallic enclosure
System Memory
Non-Volatile: no data loss
with a loss of system power
Dimensions
12.375 W x 10.25 H x 4.75 D
TEL 918-627-5530 n
FAX 918-641-7336
Certification
Environmental Specifications
Ambient Operating Temperature Range
-4°F to 160°F / -20°C to 70°C
Storage Temperature
-4°F to 185°F / -20°C to 85°C
Relative Humidity
0 to 90% RH, non condensing