Daikin FXZQ-M Series Engineering Data page 33

R-410a, 4-way ceiling mounted cassette unit 2' x 2'
Table of Contents

Advertisement

Installation and Operation
Note 2 : Factory settings of the Second code No. are marked in grey
backgrounds.
Note 3 : Only use in combination with optional remote sensor or when
setting 10-2-03 is used.
Note 4 : If group control is selected and remote control sensor is to be
used, then set 10-6-02 & 10-2-03.
Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the
same time, then setting 10-2-01, 10-2-02 or 10-2-03 have
priority.
Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the
same time, then setting for group connection, 10-6-01 has
priority and for individual connection, 10-2-01, 10-2-02 or 10-2-
03 have priority.
Note 7 : More settings for Differential automatic change over
temperatures are:
Second code No.
05
06
12-2 Control by 2 Remote Controllers (Controlling
1 indoor unit by 2 remote controllers)
When using 2 remote controllers, one must be set to "MAIN"
and the other to "SUB".
12-3 Main/Sub changeover
1. Insert a wedge-head screwdriver into the recess between
the upper and lower part of the remote controller and,
working from the 2 positions, pry off the upper part. (See
figure 14)
(The remote controller PC board is attached to the upper
part of the remote controller.)
2. Turn the main/sub changeover switch on one of the two
remote controller PC boards to "S". (See figure 17)
(Leave the switch of the other remote controller set to "M".)
1
Remote controller PC board
2
Factory setting
3
Only one remote controller needs to be changed
12-4 Computerized control (forced off and on/off
operation)
1. Wire specifications and how to perform wiring.
• Connect input from outside to terminals T1 and T2 of
the terminal board (remote controller to transmission
wiring).
Wire specification
Sheathed vinyl cord or cable (2 wire)
Gauge
Length
Contact that can ensure the minimum
External terminal
applicable load of 15 V DC, 10 mA
See figure 11
1
Input A
2. Actuation
• The following table explains "forced off" and "on/off
operations" in response to input A.
Forced off
input off  on: turns on the unit
Input "on" stops
operation
(impossible by remote controllers)
input on  off: turns off the unit
Input "off" enables
control
32
7.2°F
9°F
AWG18-16
≤328 ft
on/off operation
(by remote controller)
3. How to select forced off and on/off operation
• Turn the power on and then use the remote controller to
select operation.
• Set the remote controller to the field set mode. For
details, refer to the chapter "How to set in the field", in
the manual of the remote controller.
• When in the field set mode, select mode No. 12, then set
the first code (switch) No. to "1". Then set second code
(position) No. to "01" for forced off and to "02" for on/off
operation. (forced off at factory set.) (See figure 23)
1
Second code No.
2
Mode No.
12-5 Centralized control
For centralized control, it is necessary to designate the group
No. For details, refer to the manual of each optional controller
for centralized control.
13. INSTALLATION OF THE DECORATION
PANEL
Read the chapter "Test operation" on page 32 before making
a test run without attaching the decoration panel.
Refer to the installation manual delivered with the decoration
panel.
After installing the decoration panel, ensure that there is no
space between the unit body and decoration panel. Otherwise air
may leak through the gap and cause dewdrop. (See figure 16)
14. TEST OPERATION
Refer to the installation manual of the outdoor unit.
 The operation lamp of the remote controller will blink when
an error occurs. Check the error code on the liquid crystal
display to identify the trouble. An explanation of error codes
and the corresponding trouble are provided on "Caution for
servicing" of the outdoor unit.
If any of the items in the table below are displayed, there may
be a problem with the wiring or power, so check the wiring
again.
Remote control
display
 There is a short circuit at the FORCED
"Concentrated
Management" is lit up
OFF terminals (T1, T2)
 The power on the outdoor unit is OFF.
 The outdoor unit has not been wired for
"U4" is lit up
power supply.
"UH" is lit up
 Incorrect wiring for the transmission
wiring and/or FORCED OFF wiring.
 The power on the indoor unit is OFF.
 The indoor unit has not been wired
forpower supply.
No display
 Incorrect wiring for the remote controller
wiring, the transmission wiring and/or the
FORCED OFF wiring.
EDUS39-800-F9
3 First code No.
4 Field set mode
Content
FXZQ-M

Hide quick links: