Summary of Contents for Tylo SENSE COMMERCIAL Series
Page 1
SENSE COMMERCIAL 2017-03-16 SVENSKA РУССКИЙ INSTALLATIONSANVISNING ИНСТРУКЦИИ ПО УСТАНОВКЕ ENGLISH POLSKI INSTALLATION GUIDE INSTRUKCJA INSTALACJI DEUTSCH NEDERLANDS INSTALLATIONSANLEITUNG INSTALLATIEHANDLEIDING FRANÇAIS NOTICE D’INSTALLATION 2900 5300...
Page 2
WARNING! • Poor ventilation or heater positioning may lead to dry distillation, posing a fi re risk under certain circum- stances! • Insuffi cient insulation of the sauna cabin may pose a fi re risk! • Use of the wrong materials in the sauna cabin, such as particle board, drywall, etc., may pose a fi re risk! •...
PRIOR TO INSTALLATION Installation requirements To ensure safe use of the heater, check that the following criteria Parts are met: Check that the following parts are included in the packaging: • Cable (EKK) or electrical ducting (Fk) for connecting the hea- ter must be run on the outside of the heat insulation.
Page 4
Positioning the heater - normal installation DANGER! No more than one heater may be instal- led in the same sauna cabin. Position the sauna heater: • on the same wall as the door (or the side wall if very close to the door wall).
Page 5
If the wall on which the sensor is to be installed is made of highly Sense Commercial 6-8-10: 1900 mm heat-absorbing material (e.g. concrete, brick, etc.), or of hardened Sense Commercial 16-20: 2100 mm glass, the sensor may be installed in the ceiling at a distance from 10.
Positioning the outlet vent DANGER! The air exhaust vent must not lead out- doors. This could cause the ventilation direction to be reversed, which may negatively aff ect the heater temperature cut-out. DANGER! Any gap above the sauna ceiling should not be sealed without leaving at least one vent hole on the same wall as the sauna door! Position the outlet vent •...
Page 7
Figure 13: Dimensioning 1. 262 mm 2. 270 mm 3. 532 mm 4. 206 mm Fit herb bowl/air humidifi er (see Fig. 14). Figure 16: Electrical wiring 1. Electrical cable 2. Terminal for connection of electrical cable Connect the control panel, relay box (RB30) (if applicable) and lighting (if applicable) according to the wiring diagram.
Page 8
Figure 18: Dimensioning 1. 599 mm 2. 270 mm 3. 426 mm 4. 310 mm Figure 21: Installing the sensor Sauna heater installation Sense Commercial 6-20 (Fig. 19-22) Hang the heater on the screws see Fig. 19. Figure 22: Wiring through the wall. Unusual voltages/numbers of phases Contact Tylö...
CONNECTION/WIRING DIAGRAM WIRING DIAGRAM 200-240 V~ A B C D 200-208 V~ 230-240 V~ mm² mm² Figure 23: Control panel TS 30-012, TS 30-6 1. Sauna heater Sense Commercial 6-8 2. Control panel TS 30-012, TS 30-6 RJ10 4P4C 3 x 1.5 mm² RJ10 4P4C * ** RJ10 4P4C...
Page 10
WIRING DIAGRAM 200-240 V 3~ A B C D 200-208 V 3~ 230-240 V 3~ kW Amp mm² mm² 10.7 31 L2 L3 Fig 25: Control panel TS 30-012, TS 30-6 1. Sauna heater Sense Commercial 6-8-10 2. Control panel TS 30-012, TS 30-6 1 2 3 1 2 3 200-...
Page 11
WIRING DIAGRAM 400-415 V 3~ 400 V 3 ~ A B C D kW Amp mm² 10.7 16 L2 L3 Fig 28: Control panel TS 30-012, TS 30-6 1. Sauna heater Sense Commercial 6-8-10 2. Control panel TS 30-012, TS 30-6 400 V 3 ~ kW Amp mm²...
WIRING DIAGRAM 400-415 V 3N~ 400 V 3 ~ kW Amp mm² Max 500W ² 2.5 mm 10.7 16 L2 L3 N Fig 31: Control panel TS 16-6B 1. Sauna heater Sense Commercial 6-8-10 2. Control panel TS 16-6B RJ10 4P4C 3 x 1.5 mm²...
Need help?
Do you have a question about the SENSE COMMERCIAL Series and is the answer not in the manual?
Questions and answers