Attention
Resolution of the PT1000 sensor: 1 Fahrenheit or
0.6 Centigrade.
Do not use the datapoint associated to PT1000 in
control logic which requires a resolution less than
1 Fahrenheit.
The analog input with PT1000 can be used in
control loops only when connected to
CPO-VAV2A via a transducer with 0-10V rating.
Additionally, you must use the ComfortPoint Open
Studio tool to define custom characteristics which
matches the selected transducer.
The PT1000 sensors connected directly with
CPO-VAV2A can be used only for monitoring and
reporting purposes.
The connection between CPO-VAV2A and wall modules are
illustrated in Figure 15 through Figure 21.
1
COM
2
SENSOR
3
SETPOINT
T7460
4
BYP/FAN
Terminals
5
LED
6
BYP/RTN
7
LED/RTN
Figure 15 Connection of T7460 with the CPO-VAV2A
1
COM
2
SENSOR
3
SETPOINT
T7560
4
BYP/FAN
Terminals
5
LED
6
Bypass**
7
Humidity
8
24 Vac
Figure 16 Connection of T7560 with CPO-VAV2A
Attention
The CPO-VAV2A controller does not control the
LCD display of the T7560 Wall module. It handles
the temperature sensor input, Bypass/Fan, or Fan
Control Input. The LCD Display must not be used
to get the Effective Occupancy state of the
controller.
1
AGND
2
Temp
VAV
3
Set Point
Terminals
4
ByPass/Fan
5
LED
1
AGND
2
Temp
VAV
3
Set Point
Terminals
4
ByPass/Fan
5
LED
COM
CO2 Output 0...10V
24 VAC/DC
C7110D
NTC 20kOhm
Terminals
SETPT. 1...10kOhm
LED INPUT
OCCUPANCY
Figure 17 Connection of C7710D with CPO-VAV2A
V+
Com AC/DC
TEMP
C7262A
TEMP
Terminals
OUT1: CO2
OUT2: CO2
RELAY NO
RELAY NO
Figure 18 Connection of C7262A with CPO-VAV2A
Common
Setpoint
MSTP+
CP-CM
Temperature Sensor
Terminals
MSTP-
24 Vac/dc input
Figure 19 Connection of CP-CM with CPO-VAV2A
24 Vac/dc input
Occupancy
(24Vac input contact)
Temperature Sensor
CP-WM
Terminals
Setpoint
FAN/Bypass
Common
Figure 20 Connection of CP-WM-VAV with CPO-VAV2A
Figure 21 Connection of TR40 and TR42 with CPO-VAV2A
9
TERMINAL SETTINGS
1
A1
1
2
AGND
2
AGND
VAV
3
3
Temp
Terminals
4
4
Set Point
5
5
ByPass/Fan
6
6
LED
7
1
1
A1
2
2
AGND
3
3
AGND
VAV
4
4
Temp
Terminals
5
Set Point
6
ByPass/Fan
7
LED
1
1
AGND
2
2
Temp
VAV
3
3
Set Point
Terminals
4
ByPass/Fan
5
LED
6
1
1
AGND
2
2
Temp
VAV
3
Set Point
Terminals
3
ByPass/Fan
4
LED
5
6
EN1B-0022 IE10 R0717