7.8.3

GET/PUT connection parameter assignment

The GET/PUT instructions connection parameter assignment is a user aid for configuring S7
CPU-CPU communication connections.
After inserting a GET or PUT block, the GET/PUT instructions connection parameter
assignment is started:
The inspector window displays the properties of the connection whenever you have selected
any part of the instruction. Specify the communication parameters in the "Configuration" tab
of the "Properties" for the communication instruction.
After inserting a GET or PUT block, the "Configuration" tab automatically appears and the
"Connection parameters" page is immediately shown. This page allows the user to configure
the necessary S7 connection and to configure the parameter "Connection ID" that is
referenced by the block parameter "ID". A "Block parameters" page allows the user to
configure additional block parameters.
Note
V4.0 CPU program GET/PUT operation is not automatically enabled
A V3.0 CPU program GET/PUT operation is automatically enabled in a V4.0 CPU.
However, a V4.0 CPU program GET/PUT operation in a V4.0 CPU is not automatically
enabled. You must go the CPU "Device configuration", inspector window "Properties"tab,
"Protection" property to enable GET/PUT access (Page 82).