Easy to communicate between devices
7.5 PROFINET
TCON_Param
Table 7- 3
Structure of the connection description (TCON_Param)
Byte
Parameter and data type
0 ... 1
block_length
2 ... 3
id
4
connection_type
5
active_est
6
local_device_id
7
local_tsap_id_len
8
rem_subnet_id_len
9
rem_staddr_len
10
rem_tsap_id_len
11
next_staddr_len
138
Description
UInt
Length: 64 bytes (fixed)
CONN_OUC
Reference to this connection: Range of values: 1 (default) to 4095.
(Word)
Specify the value of this parameter for the TSEND_C, TRCV_C or
TCON instruction under ID.
USInt
Connection type:
17: TCP (default)
18: ISO-on-TCP
19: UDP
Bool
ID for the type of connection:
TCP and ISO-on-TCP:
UDP: FALSE
USInt
ID for the local PROFINET or Industrial Ethernet interface:
1 (default)
USInt
Length of parameter local_tsap_id used, in bytes; possible values:
TCP: 0 (active, default) or 2 (passive)
ISO-on-TCP: 2 to 16
UDP: 2
USInt
This parameter is not used.
USInt
Length of address of partner end point, in bytes:
0: unspecified (parameter rem_staddr is irrelevant)
4 (default): Valid IP address in parameter rem_staddr (only for
TCP and ISO-on-TCP)
USInt
Length of parameter rem_tsap_id used, in bytes; possible values:
TCP: 0 (passive) or 2 (active, default)
ISO-on-TCP: 2 to 16
UDP: 0
USInt
This parameter is not used.
FALSE: Passive connection
TRUE: Active connection (default)
Easy Book