Thermocouple Type; A.8.5 Thermocouple Type - Siemens SIMATIC S7-1200 Manual

Easy book
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Technical specifications
A.8 RTD and Thermocouple modules
Technical data
Isolation
Field side to logic
Field to 24 VDC
24 VDC to logic
Channel to channel isolation
Accuracy (25 °C / -20 to 60 °C)
Repeatability
Maximum sensor dissipation
Measuring principle
Module update time
Cold junction error
Cable length (meters)
Wire resistance
A.8.5

Thermocouple type

Table A- 54
Thermocouple type (ranges and accuracy)
Type
Under range
minimum
J
-210.0 °C
K
-270.0 °C
T
-270.0 °C
E
-270.0 °C
R & S
-50.0 °C
B
0.0 °C
--
N
-270.0 °C
324
Nominal
range low limit
1
-150.0 °C
-200.0 °C
-200.0 °C
-200.0 °C
100.0 °C
200.0 °C
800.0 °C
-200.0 °C
RTD and Thermocouple (TC)
500 VAC
SM RTD and SM TC: 500 VAC
(Not applicable for SB RTD and SB TC)
SM RTD and SM TC: 500 VAC
(Not applicable for SB RTD and SB TC)
SM RTD: None
(Not applicable for SB RTD)
SM TC: 120 VAC
(Not applicable for SB TC)
See the RTD/TC type tables:
RTD (Page 326)
TC (Page 324)
±0.05% FS
RTD: 0.5 mW
TC: Not applicable
Integrating
See the RTD/TC filter selection tables:
RTD (Page 327)
TC (Page 325)
RTD: Not applicable
TC: ±1.5 °C
100 meters to sensor max.
RTD: 20 Ω, 2.7 Ω for 10 Ω RTD max.
TC: 100 Ω max.
Nominal
Over range
range high
maximum
limit
1200.0 °C
1450.0 °C
1372.0 °C
1622.0 °C
400.0 °C
540.0 °C
1000.0 °C
1200.0 °C
1768.0 °C
2019.0 °C
800.0 °C
--
1820.0 °C
1820.0 °C
1300.0 °C
1550.0 °C
Normal range
Normal range
3,
accuracy
accuracy
2
4
@ 25 °C
-20 °C to 60 °C
±0.3 °C
±0.6 °C
±0.4 °C
±1.0 °C
±0.5 °C
±1.0 °C
±0.3 °C
±0.6 °C
±1.0 °C
±2.5 °C
±2.0 °C
±2.5 °C
±1.0 °C
±2.3 °C
±1.0 °C
±1.6 °C
Manual, 03/2014, A5E02486774-AF
3, 4
Easy Book

Hide quick links:

Advertisement

Table of Contents
loading