Alarm-Relay (X2) - ABB EDS500 Series Manual

Hide thumbs Also See for EDS500 Series:
Table of Contents

Advertisement

Device description
Pin allocation power supply (X1)
1
2
3
Due to the internal overvoltage protection, interrupt any connection to ground of the
device for the time of the measurement before you carry out isolation measurement. This
includes the earthing of the hat rail as well as all shields of all transmission lines and supply
feedings. RJ-12 plugs or RJ-45 plugs can establish earthing via the shield.
4.7.6

Alarm-Relay (X2)

The devices are equiped with a potential free alarm output (relay with isolated switchover
contact). This output corresponds to a device alarm and is activated when the device looses
the power supply or the alarm LED is constantly on (see Chapter 4.8, "Display elements"). The
reason for the signalling of an alarm can be referenced in the system alarm table (EDS500
Manual - Part 2: Alarms and alarm configuration).
Alarm output (X2)
Type of switch
Switching voltage
Switching current
Plug type
Circuit classification
Overvoltage protection
Electrical fast transient / Burst, IEC 61000-4-4 4 kV (level 4), criterion A
Surge 1.2/50 µs, IEC 61000-4-5
Conducted disturbances, induced by radio-
frequency fields, IEC 61000-4-6
Conducted, common mode disturbances
in the frequency range 0 Hz to 150 kHz,
IEC 61000-4-16
Pin allocation alarm output (X2)
1
2
3
1KGT150966 V000 1
Pin
Signal
4
1
24-60 V DC
2
Functional earth (internally wired to pin 4)
3
GND
4
Functional earth (internally wired to pin 2)
Pin
Signal
4
1 & 2
Normal state
1 & 3
Alarm state
4
Common contact (connected to 1)
A D V I C E
Toggle (potential free)
60 VDC / 25 VAC
500 mA
Phoenix Contact MSTBT 2,5/4-ST
SELV (acc. IEC 60950-1)
line to earth ±4 kV, line to line ±2 kV
4 kV (level 4), criterion A
10 V (level 3), criterion A
30 V continuous disturbance/ 300 V short
duration disturbance (level 4), criterion A
Connections
35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

500nmd01500nmd02500nmd11500nmd20

Table of Contents