The averaging model is shipped with both switches set
to ON, resulting in a device address of 203. Device
addresses can be DIP switch set from 200 to 203; see
Figure 4 and Table 1 for more details.
O
N
Figure 4: Dual-Switch
DIP Switch Block
Table 1: Network Sensor Addressing
DIP Switch
Switch 2
Address
200
OFF
201
OFF
202
ON
203
ON
Technical Specifications
Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors with LCD (Part 1 of 2)
Supply Voltage
Current
Temperature
Consumption
Only Models
Temperature
and Humidity
Models
Terminations
Network
NS-BHx7003-0,
Sensor
NS-BPB7003-0,
Addressing
NS-BTB7003-0
Models
All Other
Models
Wire Size
Modular Jack
Models
Screw
Terminal Block
Models
Communication Rate
Temperature Measurement
Range
Humidity
Full Range
Measurement
Calibrated
Range
Range
Temperature Sensor Type
Humidity Sensor Type
Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors with LCD
ON
2
1
Switch 1
OFF
ON
OFF
ON
9.8 to 16.5 VDC; 15 VDC Nominal (From SA Bus)
21 mA Maximum (Non-transmitting)
25 mA Maximum (Non-transmitting)
Modular Jack or Screw Terminal Block
DIP Switch Set from 200 to 203; Factory Set at 203
Fixed Address of 199
24 or 26 AWG (0.5 or 0.4 mm Diameter); Three Twisted Pair (Six Conductors)
18 to 22 AWG (1.0 to 0.6 mm Diameter); 22 AWG (0.6 mm Diameter) Recommended
Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
32.0°F/0.0°C to 104.0°F/40.0°C
0 to 100% RH
10 to 90% RH
Local 1k Ohm Platinum Resistance Temperature Detector (RTD); Class A per IEC
60751
Thin Film Capacitive Sensor
Repair Information
If the NS Series Network Sensor fails to operate within
its specifications, replace the unit. For a replacement
network sensor, contact the nearest Johnson Controls
representative.
Installation Instructions
5
Need help?
Do you have a question about the NS Series and is the answer not in the manual?
Questions and answers