Siemens RDU340 Basic Documentation page 13

Flush-mounted room temperature controllers for vav / cav applications, with lcd
Hide thumbs Also See for RDU340:
Table of Contents

Advertisement

Output signal inversion
Floor temperature
limitation function
Recommended values
for P51:
Parameter P51
OFF
OFF
10...50 ˚C
10...50 ˚C
Siemens
Building Technologies
The output signal of the air flow (DC 0..10V) can be limited to a minimum value by
using parameter P63 and to a maximum value using parameter P64. These air flow
limitation values can be set between 0% and 100%.
This is used to ensure a minimum or maximum supply air volume.
The output signals DC 0...10V can be inverted by means of DIP switch #2.
– If DIP switch #2 is set to "OFF", 0V corresponds to 0% travel and 10V to 100%
(factory settting).
– In position ON, 0V corresponds to 100% travel and 10V to 0% travel.
This function is useful in conjunction with normally open valves.
The floor temperature should be limited for 2 reasons: Comfort and protection of
the floor.
The floor temperature sensor, connected to multifunctional input X1, acquires the
floor temperature. If the floor temperature exceeds the parameterized limit
(parameter P51), the heating valve is fully closed until the floor temperature drops
to a level 2 K below the parameterized limit.
This function is factory-set to OFF (disabled).
Input X1 or X2 must be commissioned accordingly (P38 = 1).
See section 4.8"Multifunctional input".
Living rooms:
Up to 26 °C for long-time presence, up to 28 °C for short-time presence.
Bath rooms:
Up to 28 °C for long-time presence, up to 30 °C for short-time presence.
The table below shows the relation between parameter, temperature source and
temperature display:
External temp.
Source for display of
sensor available
room temperature
No
Built-in sensor
Yes
External temp. sensor
No
Built-in sensor
Yes
Built-in sensor
RDU340... Basic Documentation
Functions
T
Room temperature
Y10
Control output
W
Room temperature setpoint
XpH
Proportional band Heating
XpC
Proportional band Cooling
Vmin
Minimum limitation air flow
Vmax
Maximum limitation air flow
Output control
according to
Built-in sensor
External temp. sensor
Built-in sensor
Built-in sensor + limit
by external sensor
Floor temp.
limit. function
Not active
Not active
Not active
Active
13 / 32
CE1P3078en
2014-11-03