Natural Gas Piping; Pressure Testing The Gas Piping - Patterson-Kelley P-K STORM ST-1250 Installation & Owner's Manual

Gas fired boiler w/ nuro control system. natural gas boilers
Table of Contents

Advertisement

Natural Gas Piping

The table below should be used to size the natural gas piping to the appliance. The approximate
energy content of natural gas is 1,000 BTU / cu. Ft:
Nominal
Equivalent Pipe
Internal
Iron Pipe
Length
Diameter
Size
(Inches)
(Inches)
90 ° Elb
(Feet)
2
2.067
2- 1/2
2.469
3
3.068
4
4.026

Pressure Testing the Gas Piping

The appliance and all gas piping connections should be pressure-tested and must be checked for leaks
before being placed into service. The appliance must be disconnected at the manual shut-off valve
(located at the end of the supplied gas train) from the gas supply piping during any pressure testing of
the system at pressures in excess of 0.0723 psig (2" W.C.). Perform the pressure test with compressed
air or inert gas if possible.
Some leak test methods, including the use of soap and water, may cause corrosion of the carbon steel
gas pipe fittings. If using soap and water or a similar leak test method, make sure to clean off all
moisture from the gas pipe fittings prior to placing the appliance into service.
Revised: October 2, 2019
Released: October 2, 2019
Pipe Capacity for Natural Gas
Maximum Capacity in Cubic Feet of Natural Gas Per Hour
Pressure Drop of 0.5" W.C.
Equivalent Length of Pipe (in feet)
Tee
(Feet)
5.17
10.3
6.16
12.3
7.67
15.3
10.1
20.2
15800
 Patterson-Kelley 2019
All Rights Reserved.
20
40
60
2750
-
-
4350
3000
2400
7700
5300
4300
10900
8800
P-K Storm
TM
Gas Fired Boiler
Technical Service 1.877.728.5351
80
100
-
-
2050
1850
3700
3250
7500
6700
2691000099 P-K Storm Installation and Owners
150
200
-
-
1500
-
2650
2280
5500
4600
Manual.docx
Page 38

Advertisement

Table of Contents
loading

This manual is also suitable for:

P-k storm st-1500P-k storm st-2000P-k storm st-1750

Table of Contents