EMERGENCY LIGHTING CONTROL DEVICE
! IMPORTANT SAFEGUARDS !
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
ALL SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL
• This product is intended for use with lighting fixtures controlled by an emergency panel. Any switching
between backup power and utility power must be done upstream of this device.
• All wiring connections and mounting styles must be in accordance with the National Electrical Code (NEC),
National Fire Protection Association (NFPA), National Electrical Safety Code, state and local codes, and any
other regulations set forth by the local Authority Having Jurisdiction (AHJ).
• Per NFPA 70E, the use of Personal Protective Equipment (PPE) may be required. Check state and local codes.
• The load's operating voltage must be the same as the emergency power input voltage.
• To reduce the risk of electrical shock, fire, and injury to persons:
1. Disconnect all sources of power before servicing,
2. Mount this device in locations and at heights where it will not be readily accessible to tampering by
unauthorized personnel,
3. Do not mount near gas or electric heaters,
4. Do not let any wires touch hot surfaces, and
5. Do not use outdoors (NEMA 1 rating only).
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• Do not use this device for other than intended use. Generator or inverter supplied emergency panel is
required (120 or 277 VAC, 50/60 Hz).
CAUTION:
NOTE:
AVAILABLE. AN UNSWITCHED SOURCE OF NORMAL POWER IS REQUIRED. A SEPARATE CONNECTION TO A
GENERATOR-SUPPLIED (OR CENTRAL INVERTER SYSTEM-SUPPLIED) CIRCUIT MUST ALSO BE PROVIDED.
236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com
SAVE THESE INSTRUCTIONS
THIS UNIT HAS MORE THAN ONE POWER SUPPLY CONNECTION POINT. TO REDUCE
THE RISK OF ELECTRIC SHOCK, DISCONNECT ALL POWER SOURCES BEFORE
INSTALLING OR SERVICING THIS UNIT.
SERVICE BY QUALIFIED PERSONNEL ONLY
BEFORE INSTALLING THIS DEVICE, MAKE SURE THAT THE NECESSARY BRANCH CIRCUIT WIRING IS
Bodine © 2018 Signify Holding. All rights reserved.
WHEN USING ELECTRICAL EQUIPMENT, BASIC
SAFETY PRECAUTIONS SHOULD ALWAYS BE
FOLLOWED, INCLUDING THE FOLLOWING:
02/25/19
81000171

Advertisement

loading

Summary of Contents for Bodine GTD10DIM

  • Page 1 AVAILABLE. AN UNSWITCHED SOURCE OF NORMAL POWER IS REQUIRED. A SEPARATE CONNECTION TO A GENERATOR-SUPPLIED (OR CENTRAL INVERTER SYSTEM-SUPPLIED) CIRCUIT MUST ALSO BE PROVIDED. 02/25/19 Bodine © 2018 Signify Holding. All rights reserved. 236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com 81000171...
  • Page 2: Humidity Range

    SPECIFICATIONS ELECTRICAL SPECIFICATIONS (GTD10DIM, BLCD16DIM) 120-277VAC NORMAL POWER SUPPLY VOLTAGE 24MA MAX NORMAL POWER CURRENT DRAW 50/60HZ NORMAL POWER OPERATING FREQUENCY E M E R G E N C Y P O W E R S U P P LY V O LTA G E...
  • Page 3: Installation

    OPERATION The GTD10DIM and the BLCD16DIM will activate an emergency lighting load automatically upon the loss of normal power. If normal power is absent, the status of the load cannot be overridden. However, if the normal power is present, the emergency lighting load can be controlled by other means in order to use it as a normal lighting load, depending on the wiring setup.
  • Page 4: Wiring Diagrams

    EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER DRIVERS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAMS FIG 1 Using Emergency Lighting as Normal Lighting Automatic Emergency Transfer NORMAL/...
  • Page 5: Wiring Diagram

    YELLOW EMERGENCY NEUTRAL OR OTHER PHASE WHEN WIRING MULTIPLE UNITS TOGETHER , WHITE/BLUE OR REMOTE TEST INPUT WHITE/BLUE (GTD10DIM) TERMINAL SCREW 4 MUST BE A SHARED COMMON. (CLASS 2, DRY CONTACT INPUT) TERMINAL SCREW 4 (BLCD16DIM) TEST IS PERFORMED WHEN INPUT IS CLOSED.
  • Page 6: Testing And Troubleshooting

    TROUBLESHOOTING GUIDE TESTING AND TROUBLESHOOTING TEST PROCEDURE: FOUR OPTIONS TO TEST THE GTD10DIM AND BLCD16DIM AFTER INSTALLATION: INITIAL TEST FOR CORRECT WIRING APPLY EMERGENCY POWER TO THE EMERGENCY POWER INPUT AND NORMAL POWER TO THE NORMAL POWER INPUT. (IF USING THE WALL SWITCH INPUT, APPLY NORMAL POWER TO THE SWITCH ALSO, BUT KEEP THE SWITCH OFF/OPEN.)

This manual is also suitable for:

Blcd16dim