13.4.4 Default settings

The PR123/DC is supplied by ABB SACE with the following predefined parameters (Set A and Set B):
#
Protection
1
L
2
S
3
I
4
G
5
U
6
O T
7
K LC1
8
K LC2
9
UV
10
OV
11
RP
12
Language
13
PR021/K
14
Measuring module type
15
Rated Voltage
16
S startup
17
I startup
18
G startup
19
Password
20
Measuring interval
21
Iw
22
MCR
L3447
Model
L3728
On/Off
Thresholds
--
1 In
Off
6 In
On
4 In
Off
0.2 In
Off
50 %
--
Off
50 % I
1
Off
75 % I
1
Off
0.9 Un
Off
1.05 Un
Off
- 0,1 Pn
--
Engl
Off
--
HIGH VOLTAGE
--
500V
Off
6 In
Off
4 In
Off
1 In
--
0001
--
60 min
Off
3 In
Off
6In
Time
Curve
T.M.
102s
I
t
Off
2
50 ms
K
--
--
--
--
0.4 s
K
--
5 s
5 s
5 s
10 s
100 ms
100 ms
100 ms
40 ms
--
--
Apparatus
Doc. No.
1SDH000635R0002
ZS
Trip
--
--
Off: 0.04 s --
--
--
Off: 0.04 s On
Off
Off
Off
Off
Off
--
--
Emax DC
Scale
Page No.
66/108