11.1 Safety notes
WARNING: this symbol gives information about operations, actions or circumstances that can cause injuries to the personnel, damage
to the unit or economic losses.
Read this manual carefully and completely.
The use of this device should be reserved for qualified and expert personnel only.
If in doubt, about its safe usage, the unit must be put out of service to prevent any accidental use.
You must assume that safe usage is impossible if:
1. the unit shows visible signs of damage.
2. the unit does not function (for example with autotest or with the trip test unit).
3. the unit has been damaged in transit.
Prior to servicing and/or replacing, the circuit-breaker must be open.
Also remember to disconnect all power supplies connected.

11.1.1 Notes for dielectric stiffness tests

Dielectric stiffness tests on the releases, inputs and outputs, are not permitted.
11.2

Abbreviations and notes

Abbreviations
Abbreviations
Meaning
BA
Opening coil
BC
Closing coil
CB
Circuit-Breaker (for example Emax)
BT030
Power supply and Wireless communication unit, ABB SACE
PDA
Pocket Pc with Bluetooth
Emax
Series of ABB SACE air circuit-breakers
HMI030
Human Machine Interface
HW
Hardware
In
Rated current of the Rating Plug installed in the circuit-breaker
MT
Thermal memory
Pn
Circuit-breaker rated power
PR120/K
Internal signalling unit of alarms and trips of the circuit-breaker
PR120/V-PR120/LV
Measuring module
PR021/K
Signalling unit
PR120/D-M
Communication module
PR010/T
ABB SACE unit test
PR122/DC
Protection relay for CB Emax
PR123/DC
Protection relay for CB Emax
PR030/B
ABB SACE power supply unit
Relay
also called "protection unit" or "protection release"
TC
Trip Coil (opening solenoid)
SdZ
Zone selectivity
SW
Software
i-Test
"i-Test" button on the front of relay
Trip
CB opening, generated by the release
Un
Rated voltage
Vaux
Auxiliary power supply
Notes
A. Use the "Belden 3105A"- type two-wire cable for instance (not supplied by ABB SACE).
B. Use the "Belden 3106A"- type three-wire cable for instance (not supplied by ABB SACE).
C. The unit has a "backup-protection" function; if the first command to the opening solenoid does not open immediately the circuit-breaker (TC
partially fault), TRIP commands are repeatedly sent until the circuit-breaker opens.
The "backup" condition can be signalled by configuring the unit relays; using the "YO back" selection, it is possible to command the "opening
coil(YO)" accessory as another opening device if TC does not work.
L3447
Model
L3728
Apparatus
Emax DC
Doc. No.
1SDH000635R0002
Scale
Page No.
29/108