Cooldx; General Technical Data - Swegon CoolDX Series Installation And Maintenance Instructions Manual

Cooling units
Table of Contents

Advertisement

10

GENERAL TECHNICAL DATA

Cooling system CoolDX

CoolDX

Capacity
Size
variant
08-1
1
08-2
2
12-1
1
12-2
2
20-1
1
20-2
2
20-3
3
30-1
1
30-2
2
30-3
3
40-1
1
40-2
2
40-3
3
60-1
1
60-2
2
60-3
3
For an outdoor temperature of 28°C, 50% RH and an extract air temperature of 25°C.
1)
Sizing
There are many factors that influence what size of cooling
unit is required.
The CoolDX units have been designed to enable them to
meet many different prerequisites.
For correct sizing we refer to our ProUnit unit selection
program.
16
www.swegon.com
Rated
Rated
cool. power power req.
(kW)
(kW)
1)
10
3,69
14
5,02
14
4,95
20
6,94
14
4,95
20
6,94
26
9,88
27
9,00
32
10,66
45
16,47
39
12,24
45
14,54
58
21,42
58
18,94
69
20,20
95
33,18
Refrigerant
Minimum
data R407c (kg)
airflow
(m
/s)
3
Circuit 1
Circuit 2
1,2
1,6
0,46
1,2
2,2
0,46
1,3
2,7
0,68
1,4
2,9
0,9
1,3
2,7
0,68
1,4
2,9
0,9
2,3
3,3
0,9
2,0
4,2
1,25
2,2
4,7
1,5
3,4
5,6
1,5
2,6
5,3
1,8
2,9
5,9
2,1
5,1
8,1
2,1
4,9
8,0
2,6
4,9
8,0
3,2
7,9
11,9
3,2
GB.COOLDX.INST.090301
Power supply
Weight
3-phase, 400V, 16A
3-phase, 400V, 16A
3-phase, 400V, 16A
3-phase, 400V, 20A
3-phase, 400V, 16A
3-phase, 400V, 20A
3-phase, 400V, 25A
3-phase, 400V, 25A
3-phase, 400V, 32A
3-phase, 400V, 40A
3-phase, 400V, 40A
3-phase, 400V, 40A
3-phase, 400V, 63A
3-phase, 400V, 50A
3-phase, 400V, 63A
3-phase, 400V, 80A
We reserve the right to alter specifications.
(kg)
247
257
305
332
323
351
373
440
486
527
572
605
672
720
819
944

Advertisement

Table of Contents
loading