Commissioning
6.2 Local commissioning
6.2.11.2

P010: Language

The parameter title appears in the language selected, for parameters P000 to P010. If a
language is selected, parameter titles for the Quick Start parameters are displayed in the
auxiliary reading field.
Parameter
P010
Parameter
P000
P001
P003
P004
P005
P006
P007
P010
6.2.11.3

P001: Operation

Select the measurement mode required for the application (P001: Operation)
To measure how full the vessel is, select Level: the reading can be returned as level or as
volume:
● for a level reading, ensure P050 is set to 0: the reading returns the distance from process
empty level (Empty) to the current level
● for a volume reading, select a vessel shape at P050, and set volume parameters P051 to
P055 as required
To measure how much space remains in the vessel, select Space:
● Space returns a reading for the distance between current level and process full level
(Span)
To measure the distance from the reference point to the current level, select Distance.
32
Value
Description
0
*
Numeric/None
1
English
2
German
3
French
4
Spanish
Auxiliary reading
LOCK
OPERATION
MEAS RESP
ANTENNA
UNITS
EMPTY
SPAN
LANGUAGE
SITRANS Probe LR with mA/HART
Compact Operating Instructions, 05/2019, A5E46248119-AC