Gas Valve - State Water Heaters SBN 71-120NE Service Handbook

For self-cleaning induced draft multi flue commercial gas water heaters
Table of Contents

Advertisement

SBN TANK TYPE COMMERCIAL GAS WATER HEATER
SERVICE HANDBOOK

Gas Valve

The supply gas pressure is
normally measured at the gas
Inlet View
valve inlet gas pressure tap,
if available, when the gas is flowing.
The manifold gas pressure
is measured at the manifold
pressure tap of the gas valve
when the gas is flowing.
Gas valves used are 24 volt AC
combination-step opening gas
valves. They incorporate the
main valve and gas pressure
regulator into one body. The
Low Gas Pressure Switch, the
Supply Gas Inlet, and the
Supply Gas Pressure Tap are
shown in the Inlet View to the
right.
Top View
The top view of the gas valve,
shown on the right, shows the
Main Gas Regulator, Manifold
Pressure Tap, Top Knob, and the
Limited Bleed Vent Port. The main
gas regulator is found under the
silver cap screw. It is factory preset
to 3.5 inches W.C. and
adjusts gas pressure output
from 3.0 to 5 inches water
column. Caution: Always test
the manifold pressure at the
outlet when the gas is flowing.
©2003
Technical Training Department
10
Ashland City, Tennessee