Heater Status Menu - State Water Heaters SSED 5 Instruction Manual

Commercial electric water heaters
Table of Contents

Advertisement

Water heater status Menu
This menu displays non adjustable operational information.
Use the Up & Down Buttons to navigate to the bottom of
this menu.
top of Menu
Bottom of Menu
status
Displays the current Operating State of the control system. IE:
Heating, Standby, Fault.
elements on #
Displays the number of heating elements the control system has
energized.
eco contact
Displays the current state of the ECO high temperature limit switch
contacts.
enable / disable 1 & 2
Displays the current state, open or closed, of the two
Enable/Disable circuits (J7 socket on the CCB - see
w i r i n g d i a g r a m s) p r ov i d e d f o r ex t e r n a l s u p e r v i s o r y
c ontrols such as building EMS (Energy Management
System). Both of these Enable/Disable circuits must be
closed to "enable" heating operation. If either Enable/
Disable circuit is open for any reason heating operation will
b e "d i s a b l e d." T h e r e i s a p l u g w i t h t w o j u m p e r w i r e s
i n s t a l l e d f r o m t h e f a c t o r y i n t h e C C B J 7
to enable heating operation when external controls are not
in use.
s e r v i c e n o t e: I f a s u p e r v i s o r y c o n t r o l (s) i s u s e d t o
e n a b l e /d i s a b l e h e a t i n g o p e r a t i o n , i n s t a l l f i e l d w i r i n g
b e t w e e n t h e J 7 s o c ket o n t h e C C B a n d a s e t o f "d r y
contacts" on the external control per all applicable b u i l d i n g
c o d e s . T h i s i s a s w i t c h i n g c i r c u i t o n l y : D O N OT a p p l y
a ny ex t e r n a l vo l t a g e o r c o n n e c t a ny l o a d (I E: r e l ay c o i l)
to either circuit.
element # on
Displays the on/off status of each heating element. Yes = On,
No = Off.
alarm condition
Displays the status of the user definable Alarm Output function
- see Alarm Output Setup Menu. Yes = alarm condition has
been met, No = alarm condition has not been met.
alarm relay output
Displays the state of the normally open contacts of the Alarm
Output relay. This relay (J3 contacts on the CCB - see wiring
diagrams) is used for building EMS (Energy Management
System) notification of operational conditions such as Fault
conditions.
econoMy Mode setup Menu
This menu contains settings used to establish an "Economy
Set Point" and "Economy Mode" operating periods. This
control system feature can help reduce operating costs during
unoccupied, low load, or peak demand periods.
desktop screen during economy Mode
s o c ke t
setpoint adjustment
Adjustable user setting (2°F to 50°F - factory default is
20°F) the control system uses to calculate the "Economy
Set Point." The Economy Set Point = normal Operating Set
Point minus the programmed Setpoint Adjustment value.
22
economy Mode setup Menu

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ssed 120

Table of Contents