Control Panel Removal - Trane Water-Cooled CenTraVac S Series Installation Instructions Manual

Disassembly and reassembly units
Table of Contents

Advertisement

Disassembly
Figure 4.
Purge unit detail

Control Panel Removal

WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer's
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
Use the following steps to remove the control panel if
additional vertical clearance is required.
Note: The control panel can be rotated back and
downward on two mounting screws with wiring
remaining intact.
1. Mark and disconnect incoming wiring to the control
panel.
2. Remove the four hex head screws from the bottom of
the panel which secure the panel to the lower
mounting brackets.
12
Cut for coupling
3. Loosen the two hex head screws on the back of the
panel which secure the panel to the top mounting
brackets. See
Figure
5.
Figure 5.
Control panel mounting brackets
Figure 6.
Control panel mounting brackets details
4. Two people will be needed to lift the panel clear of the
chiller. Refer to
Table 1, p. 8
Steady the panel as the top retaining screws are
removed. Then lift the panel clear. Store the panel in a
clean dry area.
for control panel weight.
CVHS-SVN04E-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cvhs

Table of Contents