Optional Hinged Waterboxes; Tightening Flanges; Flanges With 8 Or 12 Screws - Trane Water-Cooled CenTraVac S Series Installation Instructions Manual

Disassembly and reassembly units
Table of Contents

Advertisement

Figure 21. Installation of 1/8-in. GORE-TEX tape
8. Lift the suction elbow into place using a sling or chain-
fall hoist.
9. Install the suction elbow retaining hex head screws.
10. Tighten the retaining screws only "hand tight". Tighten
two retaining screws, 180 degrees apart at the
compressor connection. Then tighten two screws,
180 degrees apart at the evaporator connection.
Alternate between connections until all retaining
screws are tight. Monitor the dial indicators to ensure
that there is no more than 0.010 inches of compressor
movement. If there is more movement than this,
loosen all of the screws, "zero" the dial indicators, and
repeat the procedure. Refer to
p. 21
for screw tightening sequences.
11. Reconnect the economizer vent pipe. Be sure to clean
the mating surfaces and use new O-rings on the
connections. Tighten first stage volute and economizer
top flange screws; refer to
"Tightening Flanges," p.
12. Reinstall all other chiller components which were
removed.
13. Torque all screws to specifications listed in
CVHS-SVN04E-EN

"Tightening Flanges,"

Table 2, p. 21
and
21.
Table
2.
Table 2.
Screw torques for waterbox mounting
Screw Size
(in)
(mm)
1/2
13
5/8
16
Metric Screw Size (Non-Gasketed Joints or O-ring Joints)
Screw Size
M8
M10
M12
M16
M20
14. Reconnect the previously cut compressor supply and
return lines and the motor cooling lines using the
factory-supplied couplings.

Optional Hinged Waterboxes

If the chiller includes optional hinged waterboxes and if the
waterboxes have been removed for installation or service,
or if waterbox holes do not line up with the tube sheet,
perform the following procedure.
1. Move waterbox into position.
2. Install the hex head screws for the waterbox and hand-
tighten.
3. Lift and hold the waterbox as high as the screws will
allow.
4. While holding the waterbox as high as the screws will
allow, tighten the waterbox screws to the tube sheet.
Torque to specifications listed in
5. Move hinge into position.
6. Install hinge button head screws and hand-tighten.
7. Torque button head screws for center hinge section to
waterbox to specifications listed in
8. Lift lower hinge section and hold in contact with middle
hinge section.
9. Torque button head screws for lower hinge section to
tube sheet to specifications listed in
10. Torque button head screws for upper hinge section to
tube sheet to specifications listed in
Each waterbox hinge weighs 35 lb (15.9 kg); refer to
Table 1, p. 8
for condenser and evaporator waterbox
maximum weights.
Tightening Flanges

Flanges with 8 or 12 Screws

Tighten all screws to a snug tightness, following the
numerical sequence for the appropriate pattern as shown
below. Repeat this sequence to apply the final torque to
each screw.
Reassembly
Torque
(ft·lb)
(N·m)
70–100
95–136
130–190
176–258
Torque
(ft·lb)
(N·m)
12–16
16–22
24–33
33–45
48–65
65–89
130–179
177–243
239–334
324–453
Table
2.
Table
2.
Table
2.
Table
2.
21