Siemens KNX OZW775 V2.0 Quick Start Manual

Siemens KNX OZW775 V2.0 Quick Start Manual

Central communication unit with integrated web server function

Advertisement

Quick Links

5
663
CE1N5663en
29.10.2008
Central communication
unit
with integrated web server function
The central communication unit OZW775 in plants is used together with Synco
700 devices, RXB/RXL room controllers and the Synco
unit. Key features:
• Remotely operate and monitor up to 250 Synco devices in a KNX network via
ACS software and/or via web browser.
• Link to an operator station (PC/laptop with ACS) via direct connection (USB)
or telephony (RS-232 modem).
• Link to a web browser via Ethernet (Ethernet card OZZ7E5 required) and/or
via direct connection or telephony.
• Customizable user profiles for web operation.
• Customizable user texts for inputs, outputs, function blocks.
• Send fault status messages to operator stations, SMS recipients,
pagers, fax machines, e-mail recipients (message receivers).
• Periodically send system reports to message receivers.
• Storage of the last 500 faults and messages (history).
• 4 message receivers with configurable receiver types and
transmission times.
• 8 digital inputs for fault and operational status contacts.
• 8 universal inputs, configurable for analog, digital and pulse signals.
• 5 runtime totalizer meters, automatically send service alarms.
• 8 meters for pulse signals from heat, water, gas or electricity meters.
• 4 seven-day time switches to switch consumers via relays.
• 6 relays for use with 7-day time switches or as fault relays.
• 5 offline trends with 50,000 recorded values.
Avda. San Ignacio de Loyola,185
24191 - San Andrés del Rabanedo
León - España
Tel.: +34 987 248 305
Email: simelec@simelec.es
www.simelec.es
OZZ7E5
OZZ7CF
OZW775
V2.0
TM
living central apartment
Building Technologies
HVAC Products
TM

Advertisement

loading

Summary of Contents for Siemens KNX OZW775 V2.0

  • Page 1 Avda. San Ignacio de Loyola,185 24191 - San Andrés del Rabanedo León - España Tel.: +34 987 248 305 Email: simelec@simelec.es www.simelec.es OZZ7E5 OZZ7CF OZW775 Central communication V2.0 unit with integrated web server function The central communication unit OZW775 in plants is used together with Synco 700 devices, RXB/RXL room controllers and the Synco living central apartment unit.
  • Page 2 • Office and administrative buildings, residential housing. Buildings • Schools, gymnasiums, leisure facilities, hotels. • Municipal buildings, industrial buildings. • Building maintenance companies, facility management. Building operators • Real estate agencies. • District heating companies, installers, end customers. Functions Basic functions of the central communication unit OZW775: Basic functions •...
  • Page 3 Fault acknowledgement The "Local" LED blinks to indicate that a fault is unacknowledged. The LED continues to be lit until the fault is no longer pending even after the fault is acknowledged with the "Ack" button. "Ack" resets the fault relay if a fault relay is configured. The same applies to unacknowledged "System"...
  • Page 4 Product documentation Central communication Document type Document no. unit OZW775 Data sheet N5663 Installation instructions (package insert) G5663 Commissioning instructions C5663 Ethernet card OZZ7E5 Mounting instructions (package insert) M5673 Information on OZZ7E5: See this document and G5663 CF card OZZ7CF Operating instructions (package insert) B5674 Information on OZZ7CF: See this document and...
  • Page 5 Mechanical design The central communication unit consists of the housing lower section with printed circuit Basic design boards and connection terminals. The upper housing section contains the printed circuit boards. The LEDs, operating buttons, interfaces, and slots for the CF cards (compact flash memory cards) are integrated in the upper housing section.
  • Page 6: Universal Inputs

    Technical design The central communication unit contains various function blocks (FB). The functionality of the unit can be extended by connecting (binding) the digital inputs N.D1…N.D8 and the universal inputs N.X1…N.X8 to the FB inputs "d", "x", and "i" (see figure and function block description).
  • Page 7 Function blocks FB "Faults" FB "Faults" is designed for 20 fault inputs. Inputs N.D1…N.D8 (digital) and N.X1…N.X8 (digital/analog) are connected to FB inputs "x". "Relay 1" and/or "Relay 2" is activated depending on fault priority and source. FB "Faults" handles faults and failures of the Synco devices (“System“ faults) listed in the device list as well as faults at the fault inputs and faults of the central communication unit ("Local"...
  • Page 8 The central communication unit has three interfaces to communicate between unit and Interfaces user, and the interface or connection for the KNX bus. The "PC" interface is intended to directly connect a central communication unit to a local operator station. A USB cable, type A-B, is required to this end. Modem The "Modem"...
  • Page 9 Communication connections for local monitoring and alarming (USB), and for remote Monitoring, operation via modem and Ethernet. alarming The following table lists all parameters for the communication connections that can be Parameter settings for set in each message receiver. message receivers Receiver type Interface Modem type...
  • Page 10 Mounting notes You must mount the central communication unit in a cabinet or control panel. Make sure service can easily access the unit. • Standard mounting On standard rail TH 35-7.5 • Screwed-on mounting Screwed to rear wall • Mounting position Horizontal only •...
  • Page 11 Read the commissioning instructions C5663 for the associated procedure. The com- missioning instructions PDF file is saved to the CD supplied with the unit. You can also download the PDF file from www.siemens.com/synco Web server Local activation Locally activate the web server following commissioning and parameterization of the central communication unit.
  • Page 12 LED displays Run (green) Dark No operating voltage AC 24 V or unit is starting. Unit ready to operate. Flashing Communicating with ACS. Local (red) Dark No fault (normal operating state). Central communication unit faults and/or signal at fault inputs "Hours run for service reached".
  • Page 13: Maintenance

    Clean the housing only with a dry cloth. Repair The central communication unit OZW775 cannot be repaired in the field. If faulty, return to the Repair Center of the relevant Siemens Regional Company. Disposal The central communication unit is subject to directive 2002/96/EEC (WEEE, Waste of Electrical and Electronic Equipment).
  • Page 14 Requirements for pulse inputs Universal inputs continued Signal cables Recommendation: Shielded cables Signal coupling Potential-free Type of contact Impulse contact Mechanical signal source (Reed contact) Max. pulse frequency 25 Hz Min. pulse duration 20 ms (incl. max. 10 ms bounce time) Electronic signal source Max.
  • Page 15 Protocol support for connection via Protocols to send Leased line telephone service provider UCP (universal computer protocol) messages TAP (telocator alphanum. protocol) FAX protocol (fax class 2 or 2.0) GSM telephone service provider, additional AT+ (extended AT command set) Interface type TP1 (twisted pair, 1 cable pair) KNX bus 2-wire bus...
  • Page 16 Central communication unit OZW775 0.825 kg Weight OZW775 With packaging, installation instructions and CD 1.185 kg Packaging Cardboard box Ethernet card OZZ7E5 0.018 kg Weight OZZ7E5 With packaging, mounting instructions 0.044 Kg Packaging Cardboard box CF card OZZ7CF 0.010 kg Weight OZZ7CF With packaging, operating instructions 0.022 Kg...
  • Page 17 Connection diagrams Connection diagram X1 M X2 X3 M X4 X5 M X6 X7 M X8 CE- CE+ Modem RJ45 Ethernet Q73 Q74 Q83 Q84 Q11 Q12 Q21 Q22 Q31 Q32 Q41 Q42 D1…D8 Digital inputs X1…X8 Universal inputs Ground for digital inputs, measuring ground for universal inputs KNX bus connection (negative) KNX bus connection (positive) G, G0...
  • Page 18 Dimensions Standard mounting on standard rail TH 35-7.5 Screwed-on mounting Dimensions in mm ©2005-2008 Siemens Switzerland Ltd www.sbt.siemens.com/ Subject to change 18/18 Building Technologies Central communication unit OZW775 V2.0 CE1N5663en HVAC Products 29.10.2008...