Parameterization Of The Safe Outputs - GE VersaSafe VersaPoint Series User Manual

Safety logic modul , safe output 24vdc, 8pt
Table of Contents

Advertisement

5
Two-channel
Single-channel
Parameterization
Table 5-1
Parameterization of outputs
Parameterization
Assignment
Output
Switch-off delay for stop
category 1
Switch-off delay for stop
category 1
5-2
5.2

Parameterization of the safe outputs

The individual outputs of a safety module can be parameterized differently and thus
achieve different safety integrity levels (SIL, SIL CL, Cat., PL).
If the outputs are operated via two channels, the following fixed assignment applies:
OUT0_Ch1 to OUT0_Ch2
OUT1_Ch1 to OUT1_Ch2
OUT2_Ch1 to OUT2_Ch2
OUT3_Ch1 to OUT3_Ch2
If two-channel operation in the external wiring of the outputs is not required, the outputs
can be parameterized in such a way that they operate independently of one another
(single-channel).
All safe outputs must be parameterized individually. The parameterization options are
described in Table 5-1.
Value range
Remark
OUT0 - OUT3
Not assigned
The outputs that are not assigned are disabled. However, the
Assigned
monitoring of these outputs remains active.
Single-channel
In two-channel operation, the assignment of the outputs to one
Two-channel
another is specified and cannot be parameterized.
Disabled
Disabled (default): No switch-off delay.
Enabled
Enabled: The outputs are switched off once the parameterized
switch-off delay has elapsed.
Please observe the notes below this table.
1 to 63
Time conversion according to the parameterization of the "Value
range of switch-off delay for stop category 1" parameter.
Permissible value range:
OUT0 to OUT3:
Accuracy:
Please observe the notes below this table.
User manual IC220SDL953 - September 2011
150 ms to 630 s
-5% of the parameterized value - 2 ms/+0 ms
GFK-2731

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ic220sdl953

Table of Contents